Technical description of the burner
4.3
Technical data
Tab. B
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure on the socket 5)(Fig. 4) with zero pressure in the combustion chamber and at maximum burner output.
(3)
Noise emission tests carried out as per Directive EN 15036-1, with measurement accuracy ó
= ± 1.5 dB, in the manufacturer's combustion lab with
burner operating on test boiler at maximum output.
4.4
Electrical data
Tab. C
Tab. D
Model
RS 1000/M C01
RS 1200/M C01
Type
1139 T
1140 T
Output
(1)
Output
(1)
min - max
kW
1100/4000 - 10100
1500/5500 - 11100
Fuels
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Gas pressure at max. output
(2)
-
Gas: G20/G25
mbar
67.1/101.2
97.2/145
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Progressive two-stage or modulating by kit (see accessories).
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 50
Combustion air temperature
°C max
60
Noise levels
(3)
Sound pressure
Sound power
dB(A)
85
99
89.3
99.7
Weight
Kg
460
500
Model
RS 1000/M C01
RS 1200/M C01
Electrical supply
3N ~ 400V ± 10% 50 Hz
Fan motor IE2
rpm
V
kW
A
2935
400/690
22
38.6/22.3
2920
400/690
25
44.1/25.5
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
Absorbed electrical power
kW max
24
27
Protection level
IP 55
Model
RS 1000/M C01
RS 1200/M C01
Electrical supply
3N ~ 400V ± 10% 50 Hz
Fan motor IE3
rpm
V
kW
A
2880
400/690
22
38.2/22.3
2880
400/690
25
43.4/25.1
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
Absorbed electrical power
kW max
24
27.2
Protection level
IP 55