Start-up, calibration and operation of the burner
After approx 8 seconds (it depends on the duration of the pro-
gramme), the 0 value appears on the display screen, this is to in-
dicate that the restore process has been completed correctly.
NOTE:
When the restore process is successfully completed, the 0
value is shown on the display screen.
Err C information: 136 D: 1 (restore process initialised) is
displayed for a brief moment.
6.12
List of parameters
D
1
2
1
4
3
h min s
%
P
V
WARNING
WARNING
At the end of the restore process, it is neces-
sary to check the sequence of functions and
the list of parameters.
Parameter
No. of
elements
Unit of
measure-
ment
Modifica-
tion
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
Description
Min.
Max.
000
INTERNAL PARAMETERS
050
Start backup/restore process via RDI21... / PC TOOL
(set the parameter to 1)
Index 0 = create backup
Index 1 = perform restore
Negative values indicate errors
2
-
Modification
-99
2
1
0; 0
Service mode
055
Burner identification number created from the backup
on RDI21...
1
-
Reading only
0
99999999
1
0
Service mode
056
ASN number created by the backup on RDI21...
8
-
Reading only
0
127
1
0
Service mode
057
Software Version created by the backup on RDI21...
1
-
Reading only
0x100
0xFFF9
1
0
Service mode
100
GENERAL PARAMETERS
102
Control box identification date
1
-
Reading only
0
255
1
Info mode
103
Control box identification number
1
-
Reading only
0
65535
1
Info mode
104
Identification number of the group of parameters set
1
-
Reading only
0
255
1
30
Info mode
105
Version of the group of parameters set
1
-
Reading only
0
0xFFFF
1
V 01.08
Info mode
107
Software version
1
-
Reading only
0
0xFFF9
1
V 03.30
Info mode
108
Software variation
1
-
Reading only
0
225
1
1
Info mode
111
ASN number to verify the ASN number created by the
backup on RDI 21…
8
-
Reading only
0
127
1
0
Service mode
113
Burner identification
1
-
Modification
0
99999999
1
Not defined
Info Mode
with password
Service Mode
121
Manual setting of output
Not defined = automatic operation
1
%
Modification /
zero setting
0%
100%
0.1%
Not defined
Info mode
123
Minimum output step position
Index 0: BACS output
Index 1: output of the external load regulator,
analogue.
Index 2: output of the external load regulator contacts.
3
%
Modification
0%
100%
0.1%
0%; 1%; 0%
Modo Service
124
Beginning flame loss test (TÜV test)(define the
parameter at 1)(switch of flame loss fuel valves) A
negative value indicates an error (see code 150)
1
-
Modification
-6
1
1
0
Modo Service
125
Frequency of main power supply
0 = 50 Hz
1 = 60 Hz
1
-
Modification
0
1
1
0
Service Mode
126
Brightness of display
1
%
Modification
0%
100%
1%
75%
Service Mode
128
Fuel meter: Led pulse valence
(led pulses / volumetric flow units)
1
-
Modification
0
400
0.01
0
Service Mode
130
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1,
then to 2
Answer 0: process successful
Answer -1: timeout of 1_2 - sequence
1
-
Modification
-5
2
1
0
Service Mode
133
Default output for TÜV test:
Not valid for TÜV test when output is activated
2,000 ..... 10,000 = low flame or first / second / third
stage
1
%
Modification /
zero setting
20%
100%
0.1%
Not defined
Service Mode
141
Remote management of control box
0 = off
1 = Modbus
2 = reserved
1
-
Modification
0
2
1
0
Service Mode