Installation
5.15
Electrical wiring
Notes on safety for the electrical wiring
Before carrying out any maintenance, cleaning or checking oper-
ations:
If the cover is still present, remove it and proceed with the electri-
cal wiring according to the wiring diagrams.
Use flexible cables in compliance with the EN 60 335-1 standard.
5.15.1 Supply cables and external connections
passage
All the cables to be connected to the burner should be passed
through cable grommets, as shown in Fig. 37.
Key (Fig. 37)
1
Three-phase power supply
2
6-pin plug (supplied)
3
4-pin plug (supplied)
4
7-pin plug (supplied) single-phase power supply
5
External selection of the fuel
6
Remote reset
7
Gas valves seal control
8
Signal clean contacts output
NOTE:
for details of external connections, refer to the wiring diagrams in-
cluded in this booklet.
To select the fuel from the outside, provide a switching system
with a contact capable of opening the TL circuit on every rotation
of the selector.
DANGER
DANGER
➤
The electrical wiring must be carried out with the electrical supply disconnected.
➤
Electrical wiring must be made in accordance with the regulations currently in force in the country of destination
and by qualified personnel. Refer to the wiring diagrams.
➤
The manufacturer declines all responsibility for modifications or connections different from those shown in the wir-
ing diagrams.
➤
Check that the electrical supply of the burner corresponds to that shown on the identification label and in this man-
ual.
➤
The burner has been type-approved for intermittent use.
This means they should compulsorily be stopped at least once every 24 hours to enable the control box to per-
form checks of its own start-up efficiency. Normally, burner stopping is guaranteed by the boiler's thermostat/pres-
sure switch.
➤
If this is not the case, a time switch should be fitted in series to IN to provide for burner stopping at least once
every 24 hours. Refer to the wiring diagrams.
➤
The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing system,
made according to current standards. It is necessary to check this fundamental safety requirement. In the event of
doubt, have the electrical system checked by qualified personnel. Do not use the gas tubes as an earthing system
for electrical devices.
➤
The electrical system must be suitable for the maximum power absorption of the device, as indicated on the label
and in the manual, checking in particular that the section of the cables is suitable for that level of power absorp-
tion.
➤
For the main power supply of the device from the electricity mains:
- do not use adapters, multiple sockets or extensions;
- use a multiple pole switch with at least a 3 mm gap between the contacts (overvoltage category III), as envis-
aged by the present safety standards.
➤
Do not touch the device with wet or damp body parts and/or in bare feet.
➤
Do not pull the electric cables.
DANGER
DANGER
Turn off the burner's electrical supply using the
main system switch.
DANGER
Turn off the fuel interception tap.
DANGER
Avoid condensate, ice and water leaks from form-
ing.
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
5
1
6
7
8
2
3
4
Fig. 37
20108027