54
Operating
line
User level Function
Default value
Min
Max
Unit
7043
F
Burn starts since maint
0
0
65535
-
7044
F
Maintenance interval
− − −
− − − / 1
240
Months
7045
F
Time since maintenance
0
0
240
Months
7053
F
Flue gas temp limit
− − −
− − − / 0
350
°C
7054
F
Delay flue gas message
0
0
120
min
7119 F
Economy function
Locked ¦ released
Locked -
7120 E
Economy mode
Off ¦ On
Off -
7130 E
Chimney sweep function
Off ¦ On
Off -
7140 E
manual operation
Off ¦ On
Off -
7150
I
Simulation outside temperature
-
-50.0
50
°C
7170
I
Telephone customer service
-
Input / output test
7700 I
Relay test No test ¦ Everything off ¦ 1st
burner stage T2 ¦ 1st + 2nd burn stage
T2/QX4 (***) ¦ DHW pump Q3 ¦ Heating
circuit pump Q2 ¦ Heat circ mix valve op
Y1 ¦ Heat circ mix valve cl Y2 ¦ Heating
circuit pump Q6 (***) ¦ Heat circ mix
valve op Y5 (***) ¦ Heat circ mix valve
cl Y66) ¦ Relay output QX1 ¦ Relay output
QX2 (***) ¦ Relay output QX3 (***) ¦
Relay output QX4 (***) ¦ Relay output
QX21 module 1 ¦ Relay output QX22
module 1 ¦ Relay output QX23 module
1 ¦ Relay output QX21 module 2 ¦ Relay
output QX22 module 2 ¦ Relay output
QX23 module 2
No test
-
7710 (***) I
Output test UX
-
0
100
%
7711 (***) I
Voltage signal UX
0
0
10
Volt
7730
I
Outside temp B9
-
-50.0
50
°C
7732
I
Flow temp B1
-
0.0
140
°C
7734 (***) I
Flow temp B12
-
0.0
140
°C
7750
I
DHW temp B3
-
0.0
140
°C
7760
I
Boiler temp B2
-
0.0
140
°C
7820
I
Sensor temp BX1
-
-28.0
350
°C
7821
I
Sensor temp BX2
-
-28.0
350
°C
7822 (***) I
Sensor temp BX3
0
-28
350
°C
7823 (***) I
Sensor temp BX4
0
-28
350
°C
7830
I
Sensor temp BX21 module 1
0
-28
350
°C
7831
I
Sensor temp BX22 module 1
0
-28
350
°C
7832
I
Sensor temp BX21 module 2
0
-28
350
°C
7833
I
Sensor temp BX22 module 2
0
-28
350
°C
E
=End user
I
=Commissioning
F
=Heating engineer
O
=OEM
BZ
=Operating line
(*) QAA75../78.. only, (**) RIELLOtech CLIMA COMFORT only, (***) RIELLOtech CLIMA TOP only.