36
Operating
line
User level Function
Default value
Min
Max
Unit
833
F
Switching differential 2-pos
2
0
20
°C
834
F
Actuator running time
120
30
873
s
835
O
Mixing valve Xp
32
1
100
°C
836
O
Mixing valve Tn
120
10
873
s
850 I
Floor curing function
Off ¦ Functional heating ¦ Curing heating
¦ Functional/ curing heating¦ Curing/
functional heating ¦ Manually
Off -
851
I
Floor curing setp manual
25
0
95
°C
861 F
Excess heat draw
Off ¦ Heating mode ¦ Always
Always
870 F
With buffer storage tank
No ¦ Yes
Yes -
872 F
With primary controller / system pump
No ¦ Yes
Yes
882 (***)
F
Pump speed min
100
0
100
%
883 (***)
F
Pump speed max
100
0
100
%
900 F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦
Automatic
Protection mode
Cooling circuit 1
901 (**)
E
Operating mode
Off ¦ Automatic
Automatically -
902 (**)
E
Comfort cooling setpoint
24.0
15
40
°C
907 (**)
E
release
24h/day ¦ Time programs HCs ¦ Time
program 5
24 h/day
-
908 (**)
I
Flow setpoint at OT 25°C
20
8
35
°C
909 (**)
I
Flow setpoint at OT 35°C
16
8
35
°C
912 (**)
I
Cooling limit at OT (outside temperature)
20
− − − / 8
355
°C
913 (**)
F
Locking period at end of heating
24
− − − / 8
100
h
918 (**)
F
Start of summer compensation at OT
26
20
35
°C
919 (**)
F
End of summer compensation at OT
35
20
35
°C
920 (**)
F
Summer compensation setpoint increase
4
− − − / 1
10
°C
923 (**)
I
Flow setpoint min. OT 25°C
18
8
35
°C
924 (**)
I
Flow setpoint min. OT 35°C
18
8
35
°C
928 (**)
F
Room influence
80
− − − / 1
10
%
932 (**)
F
Room temp limitation
0.5
− − − /
0.5
4 °C
938 (**)
F
Mixing valve subcooling
0
0
20
°C
939 (**)
F
Actuator type
2-position ¦ 3-position
3-position
940 (**)
F
Switching differential 2-pos
2
0
20
°C
941 (**)
F
Actuator running time
120
30
873
s
942 (**)
O
Mixing valve Xp
12
1
100
°C
943 (**)
O
Mixing valve Tn
90
10
873
s
945 (**)
F
Mixing valve in heating mode
Control ¦ Open
Controls
946 (**)
F
Dewpt monitor locking time
60
− − − /
10
600 min
947 (**)
F
Flow setpt increase hygro
3
− − − / 1
10
°C
948 (**)
F
Start flow increase at R.H.
60
0
100
%
950 (**)
I
Flow temp diff dewpoint
2
− − − / 0
10
°C
962 (**)
F
With buffer storage tank
No ¦ Yes
No
E
=End user
I
=Commissioning
F
=Heating engineer
O
=OEM
BZ
=Operating line
(*) QAA75../78.. only, (**) RIELLOtech CLIMA COMFORT only, (***) RIELLOtech CLIMA TOP only.