40
Operating
line
User level Function
Default value
Min
Max
Unit
2046 (***) F
H3 Excess heat draw
Off ¦ On
On
2048 (***) F
H3 with buffer
No ¦ Yes
Yes
2050 (***) F
H2 prim contr/system pump
No ¦ Yes
Yes
Swimming pool
2055
F
Setpoint solar heating
26
8
80
°C
2056
F
Setpoint source heating
22
8
80
°C
2065 F
Charging priority solar
No ¦ Yes
No
2070
O
Swimming pool temp max
32
8
95
°C
2080 F
With solar integration
No ¦ Yes
Yes
Primary controller / system pump
2110
O
Flow temp setpoint min
8
8
95
°C
2111
O
Flow temp setpoint max
80
8
95
°C
2112
O
Flow setpoint, cooling min
8
8
20
°C
2130
O
Mixing valve boost
10
0
50
°C
2131
O
Mixing valve subcooling
0
0
20
°C
2132 O
Actuator type
2-position ¦ 3-position
3-position
2133
O
Switching differential 2-pos
2
0
20
°C
2134
O
Actuator running time
120
30
873
s
2135
O
Mixing valve Xp
32
1
100
°C
2136
O
Mixing valve Tn
120
10
873
s
2150 I
Primary controller / system pump Before
buffer st tank ¦ After buffer st tank
After buffer st tank
-
Boiler
2200 O
Operating mode
Continuous operation ¦ Automatic ¦ Auto,
extended running time
Automatically
2203
F
Release below outside temp
− − −
− − − /
-50
50 °C
2205 F
Economy mode
Off ¦ On DHW ¦ On
Off
2208 O
Full charging buffer
Off ¦ On
Off
2210 F
Setpoint
min
40
Op line
2211
OEM
Setpoint
manu-
al opera-
tion
°C
2211
O
Setpoint min OEM
40
8
95
°C
2212 F
Setpoint
max
80
Setpoint
manu-
al opera-
tion
Op line
2213
OEM
°C
2213
O
Setpoint max OEM
85
8
120
°C
2220 (***) O
Release integral stage 2
50
0
500
°C min
2221 (***) O
Reset integral stage 2
10
0
500
°C min
2232 (***) O
Damper actuator running time
60
7.5
480
s
2233 (***) O
Modulating Xp
20
1
200
°C
2234 (***) O
Modulating Tn
150
10
873
s
2235 (***) O
Modulating Tv
4.5
0
30
s
2240
O
Switching differential of the boiler
8
0
20
°C
E
=End user
I
=Commissioning
F
=Heating engineer
O
=OEM
BZ
=Operating line
(*) QAA75../78.. only, (**) RIELLOtech CLIMA COMFORT only, (***) RIELLOtech CLIMA TOP only.