48
Operating
line
User level Function
Default value
Min
Max
Unit
5954 (**)
I
Function value 1, H1
0 -100
500
-
5954 (***)
Temp value 10V H1
100 5
130
°C
5955 (**)
I
Voltage value 2, H1
10
0
10
Volt
5956 (**)
I
Function value 2, H1
70
-100 500 -
5956 (***)
Pressure value 3.5V H1
5.0 0.0
10.0
bar
5960 (***) I
Function input H3
Optg mode change HCs+DHW
¦ Optg mode changeover HCs ¦
Optg mode changeover HC1 ¦ Optg
mode changeover HC2 ¦ Optg mode
changeover HCP ¦ Heat generation
lock ¦ Error/alarm message ¦ Min flow
temp setpoint ¦ Excess heat discharge ¦
Release swimming pool ¦ Heat request
10V ¦ Pressure measurement 10V
Optg mode chan-
geover HCs+DHW
-
5961 (***) I
Contact type H3
NC ¦ NO
NO
-
5962 (***) I
Min flow temp setpoint H3
70
8
120
°C
5964 (***) I
Temp value 10V H3
100
5
130
°C
5966 (***) I
Pressure value 3.5V H3
5.0
0.0
10.0
bar
5982 (***) I
Function input EX2
Counter 2nd burner stage ¦ Heat
generation lock ¦ Error/alarm message
¦ SLT error message ¦ Excess heat
discharge
Counter for second
burner stage
-
5983 (***) I
Cont type input EX2
NC ¦ NO
NO
-
6014 I
Function mixing group 1
Heating circuit 1 ¦ Return temp controller
¦ Prim contr/system pump ¦ DHW
primary controller ¦ Instantaneous DHW
heater ¦ Return controller cascade ¦
Cooling circuit 14) ¦ Heating circuit /
Cooling circuit 1 (**)
Heating circuit
-
6015 (***) I
Function mixing group 2
Heating circuit 2 ¦ Return temp controller
¦ Prim contr/system pump ¦ DHW
primary controller ¦ Instantaneous DHW
heater ¦ Return controller cascade
6020 I
Function extension module 1
None ¦ Multifunctional ¦ Heating circuit
2 ¦ Return temp controller ¦ Solar DHW ¦
Prim contr/system pump ¦ DHW primary
controller ¦ Instantaneous DHW heater
¦ Return controller cascade ¦ Cooling
circuit 1 (**)
None -
6021 I
Function extension module 2
None ¦ Multifunctional ¦ Heating circuit
2 ¦ Return temp controller ¦ Solar DHW ¦
Prim contr/system pump ¦ DHW primary
controller ¦ Instantaneous DHW heater
¦ Return controller cascade ¦ Cooling
circuit 1 (**)
None -
E
=End user
I
=Commissioning
F
=Heating engineer
O
=OEM
BZ
=Operating line
(*) QAA75../78.. only, (**) RIELLOtech CLIMA COMFORT only, (***) RIELLOtech CLIMA TOP only.