8
INSTALLATION
INSTALLATION
8
UNPACKING THE PRODUCT
R
RBS 2S Ready-i
solar heaters are supplied in a single pack-
age on a wooden pallet.
The boiler comes with a solar station supplied with solar reg-
ulator already wired to the high-efficiency circulator, and two
non-wired probes to be inserted in the boiler sockets.
The following items are delivered in a plastic bag inside the
packaging:
− Instruction manuals
− Bar code label
− Hydraulic test certificate
− Energy label (to be applied to device upon installation)
− No. 1 solar probe PT1000.
9
The instruction manual is an integral part of the solar stor-
age cylinder. Once located, read it thoroughly and keep it
safe.
9
For handling operations, thoroughly follow the instructions
on device package label.
9
ACCESS TO THE SOLAR STATION
To access the solar station it is necessary to remove the front
panel (1) by pulling it towards yourself and lifting it up by means
of the specific handles.
1
Locate the bag containing the documentation, remove the en-
ergy label and apply it to the boiler casing
Installation
10
PLACE OF INSTALLATION
R
RBS 2S Ready-i
storage cylinders can be installed in any
room where there is no specific requirement for an electrical
protection rating higher than IP X0D.
≥ 0,3 m
≥ 0,6 m
≥ 0,3 m
≥ 0,6 m
≥ 0,7 m
NOTE:
the above-indicated dimensions are recommended for a
correct maintenance and access to the device.
9
When installing the boiler, allow sufficient space around it
to access all safety and control devices and to permit easy
maintenance.
11
INSTALLATION IN OLDER SYSTEMS AND SYSTEMS
REQUIRING MODERNISATION
When installing
R
RBS 2S Ready-i
storage cylinders in old sys-
tems or systems requiring modernisation, always perform the
following checks.
− Make sure that the system is fitted with safety and con-
trol devices in accordance with applicable legislation and
standards
− Make sure that the central heating circuit has been
flushed out to remove all sludge and lime scale, and has
been vented and seal tested
− Make sure that a suitable water treatment system is in-
stalled if the quality of the supply/recirculation water so
demands (refer to the reference values listed in the table
alongside).
12
WATER QUALITY REQUIREMENTS
REFERENCE VALUES
pH
6-8
Electrical conductivity
less than 200 μS/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0.3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 35°F
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm
The values above ensure proper operation of the system. Refer
to the limit values specified in the current standards and regu-
lations on the installation site.