TECHNICAL FEATURES    

 

The burner conforms to IP 40 level of insulation as per CEI/70.1

 

 

 

Thermal power

116/232 ÷ 465 kW  -  100.000/200.000 ÷ 400.000 kcal/h

Fuels

Oil, max. viscosity at 20°C: 6mm

 

2

 

/s (1.5°E) natural gas with

Pci 8600 kcal/m

 

3

 

Lpg with Pci 22.200 kcal/m

 

3

 

 

Minimum gas pressure
(measured at the test-point)

Maximum capacity requires 9 mbar with natural gas,
9.5 mbar with LPG. Combustion chamber at 0 mbar.

Maximum gas pressure

150 mbar

Electrical supply

Three-phase 380 V  +10%  -15%   

~

  60 Hz with neutral

Motor

1.5 A/380V

Pump-capacitor motor

1A / 220 V - 

6.3 

µF

Ignition transformer

Primary: 1.8A / 220 V  -  Secondary: 30 mA / 1x8 kV

Pump

Output 55 kg/h at 12 bar - max pressure 15 bar

Operation

Two stages

Fig. 1

EQUIPMENT

Quantity

Burner accessories

1

Gas-train’s gasket

8

Screws

1

Insulating screen

3

Seal

2

Oil hoses

4

Connectors

4

Gaskets

1

Lpg transf. kit

2

Oil nozzles

1

Flange

KEY TO LAY-OUT

1

- Oil valve 1° stage

2

- Oil valve 2° stage

3

- Safety oil valve

4

- Oil supply port

5

- Oil return port

6

- Pressure regulator at the pump

7

- Air damper motor

8

- Pressure gauge port (G 1/8)

9

- Vacuum gauge port (G 1/8)

10 - Terminal board
11 - Reset push-button of the motor

overload relay

12 - Cable gland
13 - UV photocell
14 - Oil motor capacitor
15 - Oil-gas selector switch
16 - Control-box reset button
17 - Air pressure-switch
18 - Gas pressure socket to sleeve

2

1

3

8

9

4

5

7

18

17

15

11

10

12

16

14

13

S7537

6

Summary of Contents for GI/EMME 400

Page 1: ...2915143 6 Installation use and maintenance instructions Dual fuel Gas Oil Gas burner MODEL TYPE GI EMME 400 496 T80...

Page 2: ......

Page 3: ...8A 220 V Secondary 30 mA 1x8 kV Pump Output 55 kg h at 12 bar max pressure 15 bar Operation Two stages Fig 1 EQUIPMENT Quantity Burner accessories 1 Gas train s gasket 8 Screws 1 Insulating screen 3 S...

Page 4: ...with combustion chamber at 0 mbar Boiler front plate drilling Extension that you can obtain with special extended head to be requested separately Burner 160 160 155 M10 410 610 187 320 397 97 292 165...

Page 5: ...e boiler s plate 6 interposing gasket 5 Mount the group A to the boiler front Fit the nozzles and regulate the combustion head as speci fied below S7539 6 5 4 1 3 2 B A 1 Gas supply pipe 7 Min gas pre...

Page 6: ...be disconnected with out causing any problems H Margin L Inlet pipe s length including the vertical line The copper pipes with diameter 8 and 10 shown in the schemes can be replaced with 1 4 and 3 8...

Page 7: ...aker CO Selector switch MB Burner terminal strip MP Pump motor MV Fan motor PA Air pressure switch RT Thermal relay SM Servo motor TA Ignition transformer TB Burner earth UV Probe U V V1 1 stage valve...

Page 8: ...control system PC Check pressure switch PG Min gas pressure switch TB Burner earth NOTICE The electric wiring carried out by the installer must be in compliance with the rules in force in the country...

Page 9: ...IN gland Pg 13 5 for sheath 13 To guarantee the IP 40 protection level in accordance to CEI 70 1 seal the glands that are not used NOTES Do not exchange Neutral with Phase avoid a plug socket connecti...

Page 10: ...s to holes F Nozzle 1 2 1 2 kg h bar GPH kg h GPH kg h 12 2 50 9 7 2 50 9 7 19 4 10 12 3 00 3 00 10 8 11 7 3 00 3 00 10 8 11 7 21 6 23 4 10 12 3 50 3 50 12 6 14 0 3 50 3 50 12 6 14 0 25 2 28 0 10 12 4...

Page 11: ...lever The orange lever controls the air damper position for the first flame it is adjustable both for opening and closing 2nd STAGE Red and black levers The red lever controls the air damper position...

Page 12: ...fuel In the other two situations start up the burner bleed the air of manometer joint 8 P fig 1 if you have a lock out repeat the cycle ATTENTION Before starting up the burner check that the return p...

Page 13: ...e a microammeter of 100 A c c connected to the photocell as in the scheme with a capacitor of 100 F 10V c c at the same level of the instrument BURNER STARTING UP PROGRAMME If during the work the flam...

Page 14: ...The air pressure switch does not effect a selection because of a fault contact insufficient air pressure LOCK HALT Malfunctions of the flame detection circuit photo sensitive cell exhausted fault inte...

Page 15: ......