Installation, use and maintenance instructions

2915906  (3) - 11/2012

Light oil burners 

CODE

 MODEL

TYPE

3477785

P200 T/G

477 T80

3477786

P200 T/G

477 T80

Summary of Contents for P 200 T/G

Page 1: ...Installation use and maintenance instructions 2915906 3 11 2012 Light oil burners CODE MODEL TYPE 3477785 P200 T G 477 T80 3477786 P200 T G 477 T80...

Page 2: ......

Page 3: ...30 2370 kW 45 200 kg h see page 2 Operation 1st stage 2nd stage 3rd stage Fuel Light oil max viscosity at 20 C 6 mm2 s 1 5 E Electrical supply Three phase 220V 10 10 60Hz without neutral 380V 10 10 60...

Page 4: ...urner 1st STAGE POWER AND OUTPUT MINIMUM MAXIMUM kW kg h kW kg h 1st nozzle ignition phase 391 33 782 66 1st 2nd nozzle intermediate phase 794 67 1576 133 1st 2nd 3rd nozzle operation phase 1186 100 2...

Page 5: ...oved and no prob lems arise DIMENSIONS OF THE TESTING COMBUSTION CHAMBER in compliance with ISO 5063 1978 For the combustion head projection carefully follow the boiler manufacturer indications A prop...

Page 6: ...the tap from the vacuometer plug 5 fig 1 and wait for the flow of the fuel Pay attention to do not overcome the max depression of 0 45 bar 35 cm Hg over this value the fuel may turn into gas Check th...

Page 7: ...ell RT Thermal relay h 1 1 st stage hourcounter TA Ignition transformer h 2 2 nd stage hourcounter TB Burner ground earth connection h 3 3 rd stage hourcounter VS Safety solenoid valve L1 1 st stage l...

Page 8: ...eset push button T3 3 rd stage load control system TB Burner ground earth connection 220V 380V F Ampere T35 T25 S mm2 4 0 2 5 Check the lock out by darkening the photo cell after removal of the cover...

Page 9: ...three nozzles operating the pressure increases automatically with two noz zles in operation and more with only one 1st Stage 2nd Stage A Nozzles 60 Pump 12 bar 1 Total delivery kg h GPH 1st 2nd 3rd 1s...

Page 10: ...ed at 12 bar Pay attention to not overcome the pump pressure values of 10 and 14 bar At the end on the base of the maximum output you obtain the combustion head adjustment from the diagram D The adjus...

Page 11: ...clockwise the hexagonal body 2 in order to decrease the air flow and counterclocwise to in crease it The right adjustment of the air dampers may be detect by checking the combustion results in the thr...

Page 12: ...ration are shown rightly on the 3rd nozzle hourcounter Commutator Pos 0 Burner stop Pos 1 Burner operation only at 1st stage Pos 2 Burner operation at 1st and 2nd stage Pos 3 Burner operation at 1st 2...

Page 13: ...f you desire to reduce the pre purge period from 29 5 s to 16 s with contemporaneous presence of the pre ignition remove the wire from the terminal no 7 to the no 3 of the control box maintaining the...

Page 14: ...amage to the installation On the third lockout contact the After sales Service WARNING If further lockouts or burner faults occur interventions must only be made by qualified authorised personnel as i...

Page 15: ......

Page 16: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com...