FINAL CHECKS

 (with burner running)

• Disconnect one of the wires on the minimum

gas pressure switch:

• Open remote control device TL:
• Open remote control device TS:

the burner must stop
• Disconnect the common wire P from the air

pressure switch:

• Disconnect the ionisation probe lead:
the burner must lock out
• Make sure that the mechanical locking sys-

tems on the various adjustment devices are
fully tightened.

MAINTENANCE

Notes on safety for the maintenance

The periodic maintenance is essential for the
good operation, safety, yield and duration of the
burner.
It allows you to reduce consumption and pollut-
ing emissions and to keep the product in a relia-
ble state over time.

Before carrying out any maintenance, cleaning
or checking operations:

Maintenance frequency

The gas combustion system should be checked
at least once a year by a representative of the
manufacturer or another specialised technician.

Safety test - with gas ball valve closed

It is fundamental to ensure the correct execution
of the electrical connections between the gas so-
lenoid valves and the burner to perform safely the
commissioning.
For this purpose, after checking that the connec-
tions have been carried out in accordance with
the burner's electrical diagrams, an ignition cycle
with closed gas ball valve -dry test- must be per-
formed
1

The manual ball gas valve must be closed

2

The electrical contacts of the burner limit
switch need to be closed

3

Ensures closed the contact of the low gas
pressure switch

4

Make a trial for burner ignition.

The start-up cycle must be as follows:

Starting the fan for pre-ventilation

Performing the gas valve seal control, if pro-
vided

Completion of pre-ventilation

Arrival of the ignition point

Power supply of the ignition transformer

Electrical Supply of solenoid gas valves.

Since the manual gas ball valve is closed, the
burner will not light up and its control box will go
to a safety lockout condition.
The actual electrical supply of the solenoid gas
valves can be verified by inserting a tester. Some
valves are equipped with light signals (or close/

open position indicator) that turn on at the same
time as their power supply.

The maintenance interventions
and the calibration of the burner
must only be carried out by quali-
fied, authorised personnel, in ac-
cordance with the contents of this
manual and in compliance with
the standards and regulations of
current laws.

disconnect the electricity sup-
ply from the burner by means of
the main switch of the system;

close the fuel interception tap.

DANGER

DANGER

DANGER

Summary of Contents for GAS 9/2

Page 1: ...Installation use and maintenance instructions 20014474 5 01 2018 Forced draught gas burners Two stage operation CODE MODEL TYPE 20014057 GAS 9 2 1114 T 20014058 GAS 9 2 1114 T GB...

Page 2: ......

Page 3: ...The instruction manual supplied with the burner is an integral and essential part of the product and must not be sepa rated from it it must therefore be kept carefully for any necessary consultation...

Page 4: ...expressly named by the manufacturer the type and pressure of the fuel the voltage and frequency of the elec trical power supply the minimum and maximum deliveries for which the burner has been regulat...

Page 5: ...ire and single stage on off Standard applications Boilers water steam diathermic oil Ambient temperature C 0 40 Combustion air temperature C max 60 In conformity with EEC Directives 2006 95 2004 108 2...

Page 6: ...This kit must be fitted whenever the the burner is to be operated on town gas Code is suitable for the both standard and ex tended head FLAME SENSOR KIT Code 3010359 SUPPORT D Code 3000731 The support...

Page 7: ...ts The maximum dimensions of the burner are giv en in C Bear in mind that inspection of the combustion head requires the burner to be opened by with drawing the rear part on the slide bars The maximum...

Page 8: ...ar gins of safety and therefore the entire FIRING RATE range may be used COMMERCIAL BOILERS The burner boiler combination does not pose any problems if the boiler is CE type approved and its combustio...

Page 9: ...dered Example Burner GAS 9 2 Natural gas PCI 10 kWh Nm3 curve 1 Gas pressure at test point 13 A p 5 24 mbar Pressure in combustion chamber 2 mbar 24 2 22 mbar in the GAS 9 2 graph this corresponds to...

Page 10: ...is stage slide the burner fully out from slide bars 6 Before securing the combustion head to the boiler make sure the probe and the electrode are correctly positioned as shown in C If positioning is i...

Page 11: ...or 1 to the reference position defined by the chart this moving rod and shut ter mounted inside the combustion head Positioning can be read by the index on the sector itself or on the graduated cylind...

Page 12: ...h EN 676 Standards gas valve leak detection control devices are compulsory for burners with maximum out puts of more than 1200 kW 13 Gas train burner adaptor P1 Pressure at combustion head P2 Pressure...

Page 13: ...9 A p 5 The fair leads and precut holes can be used in various ways One example is given be low GAS 9 2 1 Three phase power supply Pg 11 2 Single phase power supply Pg 7 3 Remote control device TR Pg...

Page 14: ...o MAX Even if the scale of the thermal cut out does not include rated motor absorption at 400 V protec tion is still ensured in any case N B Models GAS 9 2 three phase leave the factory preset for 400...

Page 15: ...ect position and establishes when the stage 2 gas valve will be energized It makes a maximum rotation of 90 in 5s It is equipped with 7 cams which can be adjust ed by 4 coloured levers A graduated pla...

Page 16: ...n the fol lowing sequence 1 Blue lever 2 Orange lever 3 Black lever 4 Red lever The straight line 2 A marks the lever sequence Manuel air damper section Factory is setting at 30 This damper section sh...

Page 17: ...s 3s In order to measure the firing output Disconnect the plug socket 18 A p 5 on the ionization probe cable the burner will fire and then go into lock out after the safety time has elapsed Perform 10...

Page 18: ...ention as a rule the air pressure switch must limit the CO in the fumes to less than 1 10 000 ppm To check this insert a combustion analyser into the chimney slowly close the fan suction inlet for ex...

Page 19: ...rols boiler tempera ture or pressure point C The control box will continue however to mon itor flame presence and the correct position of the air pressure switch When the temperature or the pressure i...

Page 20: ...been carried out in accordance with the burner s electrical diagrams an ignition cycle with closed gas ball valve dry test must be per formed 1 The manual ball gas valve must be closed 2 The electrica...

Page 21: ...t the burner if the combustion values found at the beginning of the operation do not comply with the regulations in force or at any rate do not correspond to good combustion Use the appropriate card t...

Page 22: ...ormer electrical connections Check 32 Control box defective Replace 33 A cock down line of the gas train is closed Open 34 Air in pipework Bleed air The burner goes to lock out right after flame appea...

Page 23: ...e signal Electrical supply lower than 170V Lock out Extraneous light Key Off Yellow Green Red SIGNAL PROBABLE CAUSE 2 flashes The flame does not stabilise at the end of the safety time faulty ionisati...