![Riello 3002949 Manual Download Page 16](http://html1.mh-extra.com/html/riello/3002949/3002949_manual_1459995016.webp)
3008
1
GB
3002949
CONTROL BOX MG569
3002967
The new control box
MG569
is installed on either single or dou-
ble stage burners, (see fig. 1).
EQUIPMENT
Control box MG569 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N° 1
Leads RS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N° 1
Leads SO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N° 1
Protection V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N° 1
Assembly connection (
only for code 3002949
) . . . . . . . . . N° 1
Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N° 1
The assembly connection (fig. 6, page 2) must be used only if
a control box model
525SE/G, 566SE, 566SE Rev. 1 and
566SE Rev. 2
needs to be replaced.
INSTALLATION
Trained personnel must carry out the substitu-
tion of the control box.
It is necessary to switch off the main power sup-
ply before effecting any substitution.
To install the new
MG569
control box, it is necessary
to use the diagram below.
To install, proceed as follows:
®
Unscrew the fixing screws and remove the burner cover.
®
Disconnect all connections, the 7-pin plug, the ioniza-
tion probe, the H.T. lead and the earth wire from the
control box.
®
Remove the control box from the burner by unscrewing
the screws (
A
, fig. 3 ) and pull in the direction of the ar-
row.
®
Install the new control box supplied by fastening it to the
burner by the screw (
A
, fig. 3), with a torque wrench set-
ting of 1 – 1.2 Nm.
®
Reconnect all connections, the 7-pin plug and the earth
wire.
REMOTE RESET CONNECTION, (fig. 4)
If the burner has a remote reset, you must proceed as fol-
lows:
®
Cut the existing socket-connection.
®
Carry out the new connection (
RS
, see electrical wiring
page 3).
®
Connect a button at 20 m. max.
RS
SO
Fig. 1
E9249
Fig. 2
ATTENTION
N
L2
R
=
=
C
S2
N
2
S1
A
M
B
A
N
1
G
E9263
SO
PA
SM
MV
V2
V1
RS
PG
KEY TO LAY-OUT, (fig. 2)
SM
- Servomotor
(for burners designed)
PG
- Gas pressure switch
MV
- Motor
V1
- 1
st
stage valve
PA
- Air pressure switch
V2
- Protection
SO
- Ionisation probe
RS
- Remote reset
MG569
568 - 569
566SE Rev. 3
MG569
525SE/G - 566SE
566SE Rev. 1 and Rev. 2
MG569 + Assem-
bly connection
Fig. 3
E9250
A
E9242
Fig. 4