- 31 -
PROGRAMMABLE AUXILIARY SOCKETS (EnergyShare)
The EnergyShare sockets are outlets that allow for the automatic disconnection of the load applied to them in certain operating
conditions. The events that determine automatic disconnection of the EnergyShare sockets can be selected by the user through
the configuration software. For example, it is possible to select disconnection after a certain period of battery operation; or
when the pre-alarm threshold for battery discharge has been reached, or when an overloading event occurs.
By default the Energyshare sockets are not configured and therefore function as other outlets.
The EnergyShare function is associated with an icon on the display whose meaning is explained in the paragraph entitled
“
Display panel messages
”.
The presence and the number of these sockets will depend upon the UPS type, these sockets are easily recognised by the
EnergyShare label located beside them.
REMOTE CONTROL TERMINAL BOARD and R.E.P.O.
The remote control terminal allows for implementation of the REPO function (Remote Emergency Power Off) and to remotely
switch ON and switch OFF the UPS.
The UPS is provided by the manufacturer with the REPO terminals short-circuited. For installation remove the short circuit and
connect to the device's normally closed contact
In case of an emergency, if the stop device is used, the REPO control is opened and the UPS goes into stand-by mode and
the load is completely disconnected.
Attention:
before restarting the UPS, reset the stop device.
The circuitry of the remote control terminal board is self-powered with SELV circuits. Therefore, an external voltage supply is
not required. When a contact is closed, a maximum current of 15mA circulates.
All connections with the remote control terminal board are made through a cable which guarantees a double insulation
connection.
Logic of the connections:
R.E.P.O.
This feature is activated by opening the contact between pin’s 1 and
2.
REMOTE ON
This feature is activated by closing the contact between pin’s 2 and 3
for a few seconds.
R
EDUNDANT AUXILIARY POWER ADAPTER FOR AUTOMATIC BYPASS
The UPS is equipped with a redundant auxiliary power adapter which permits operation on the automatic bypass even in the
event of main auxiliary power faults. If a fault occurs in the UPS shutting off the main auxiliary power supply, the load is powered
by the automatic bypass automatic bypass without any internal protection and without any limitation of the power delivered to
the load. In this emergency condition, any perturbations present on the input line affect the load. The multiprocessor board and
control panel are not powered in this mode; therefore, the LEDs and displays are off.
E
XTERNAL TEMPERATURE PROBE
This
NON-ISOLATED
input can be used to measure the temperature inside a remote Battery Box.
It is essential that only the kit provided by the manufacturer is used. Any uses not conforming to the specifications
may cause faults or breakdowns of the equipment.
To install, connect the cable included in the special kit to the "EXT BATTERY TEMP PROBE".
After installation, enable the outdoor temperature measuring function using the configuration software.