- 26 -
USE
C
ONNECTIONS AND SWITCHING ON FOR THE FIRST TIME
1) Power on the UPS.
2) Press the 1/0 switch located under the removable front panel.
3) After a few moments, the UPS will switch on, the display will light up, there will be a beep and the
icon will start
to flash. The UPS is in stand-by mode: meaning that it is only consuming a small amount of power. The microcontroller
supervising the self-diagnoses is powered; the batteries are charging; and everything is ready for UPS activation.
Battery operation is also in stand-by mode provided that the timer is active.
4) Connect the equipment to the output of the UPS using cables no longer than 10 metres.
WARNING: Do not connect the IEC 10A and 16A sockets to devices that absorb more than 10A or 16A respectively.
For equipment that exceeds these levels, use the appropriate terminals only.
5) Check which operating mode is set on the display and, if necessary, see the “
Configuring operating modes
”
paragraph to set the required mode. For advanced configurations, set up the UPS with the appropriate configuration
software.
S
WITCHING ON FROM THE MAINS
1) Press the “ON” button for 1 second. After pressing it, all the icons on the display light up for 1 second and the UPS
beeps.
2) Switch on the equipment connected to the UPS.
When switching on for the first time only:
after 30 seconds, check that the UPS is operating correctly:
1) Simulate a blackout by disconnecting power to the UPS.
2) The load must continue to be powered, the
icon on the display must light up and there must be a beep every
4 seconds.
3) When power is reconnected, the UPS must go back to operating from the mains.
S
WITCHING ON FROM THE BATTERY
1) Press the 1/0 switch located under the removable front panel.
2) Hold down the “ON” button for at least 5 seconds. All the icons on the display light up for 1 second.
3) Switch on the equipment connected to the UPS.
S
WITCHING OFF THE
UPS
In order to switch off the UPS, hold down the “STBY” button for at least 2 seconds. The UPS goes back to stand-by mode and
the
icon starts to flash:
1) If the mains power is present, the 1/0 switch must be pressed to completely turn off the UPS.
2) During battery mode operation with the timer not set, the UPS automatically switches off after 30 seconds. However
if, the timer is set, press and hold down the "STBY" key for at least 5 seconds to turn off the UPS. For complete
shutdown, press the 1/0 switch.
I
NTERNAL CLOCK SETTING
During the first installation, you must set the internal UPS clock through the configuration software. If the UPS remains off or
deactivated for more than 3 days, it will be necessary to re-configure the clock to avoid a failure of any programmed power-on
or shut-down configuration.