Pag. 21 a 83
0MLMHTK65RUENUB
Minimum Wire Size Requirements
Bypass Input (for dual input unit only)
UPS models
Phase and Neutral Conductor
Ground Wire
65 kVA
2
6 AWG
80 kVA
1/0
6 AWG
100 kVA
2/0
6 AWG
125 kVA
4/0 or 250 kcmil
4 AWG
Output
UPS models
Phase and Neutral Conductor
Ground Wire
65 kVA
2
6 AWG
80 kVA
1/0
6 AWG
100 kVA
2/0
6 AWG
125 kVA
4/0 or 250 kcmil
4 AWG
Battery
UPS models
Phase Conductor
Ground Wire
65 kVA
3/0
6 AWG
80 kVA
4/0
6 AWG
100 kVA
300 kcmil
6 AWG
125 kVA
400 kcmil
4 AWG
CAUTION:
Use at least 75
o
C rated copper wire. Minimum wire size is based on full load ratings
applied to NEC Code Table 310-16. Code may require a larger AWG size than shown in this table
because of temperature, number of conductors in the conduit, or long service runs. Follow local
requirements. Branch circuit protection must be provided for the input circuits as part of the
installation.
Input (for single input unit)
UPS models
Phase and Neutral Conductor
Ground Wire
65 kVA
1
6 AWG
80 kVA
2/0
6 AWG
100 kVA
3/0
6 AWG
125 kVA
250 kcmil
4 AWG
Rectifier Input (for dual input unit only)
UPS models
Phase Conductor
Ground Wire
65 kVA
1
6 AWG
80 kVA
2/0
6 AWG
100 kVA
3/0
6 AWG
125 kVA
250 kcmil
4 AWG