Thank you for choosing our product.
RPS S.p.A. is highly specialized in the development and production of uninterruptible power systems (UPS). The
UPS’s of this series are high quality products, carefully designed and manufactured to ensure optimum
performance.
Applicability
This manual applies to the following models:
MASTER HP-UL 65-00
65 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta (see below); “00” may be
replaced with an alternate two character designator that denotes installed options as described in the order
documentation.
MASTER HP-UL 80-00
80 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta (see below); “00” may be
replaced with an alternate two character designator that denotes installed options as described in the order
documentation.
MASTER HP-UL 100-00
100 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta (see below); “00” may be
replaced with an alternate two character designator that denotes installed options as described in the order
documentation.
MASTER HP-UL 125-00
125 kVA, 480 V input, 480 V output, 60 Hz, configured as wye-wye or delta-delta (see below); “00” may be
replaced with an alternate two character designator that denotes installed options as described in the order
documentation.
The wye output configuration that provides an output neutral connection is only permitted when an input neutral is
provided; that is, the delta-wye configuration is prohibited. The source must have a grounded neutral, even if the
neutral is not connected to the UPS; that is, a delta source may not be ungrounded or corner grounded. Please refer
to Section 4.4 for additional information.
SAFETY WARNINGS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for Models 65, 80, 100, 125 kVA MASTER HP-UL UPS that should
be followed during installation and maintenance of the UPS. Please read all instructions before operating the
equipment and save this manual for future reference.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
a. Do not use outdoors.
b. Do not route wiring across or near hot surfaces.
c. Do not install near gas or electric heaters.
d. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on
skin or in eyes, flush acid with fresh water and contact a physician immediately.