Risk of overturning
In order to avoid the risk of the device overturning, ensure that it is firmly secured to the fork-lift truck by
means of appropriate ropes before moving it.
When being moved the cabinet should be handled with care; shocks or drops can damage it. Once in position,
remove the packaging carefully in order not to scratch the device.
The packaging should be removed as follows:
1.
Cut the bands
2.
Slide away the carton from above.
3.
Remove the screws securing the cabinet to the wooden base.
Installation environment
The UPS and the battery cabinet have been designed for indoor installation. The choice of premises for installation
should comply with the points set out below.
Ambient conditions:
ensure that the floor can support the weight of the FIRSTLINE and of any battery cabinet that may be
used
avoid dusty environments (the indoor area must be free of conductive contaminations)
avoid narrow environments that could hinder normal maintenance operations
avoid placing the device in areas exposed to direct sunlight or heat
ensure that the ambient temperature conforms to the following:
-
minimum operating temperature:
+32°F ( 0 °C)
-
maximum temperature for 8 hours a day:
+104°F (+ 40°C)
-
average temperature for 24 hours:
+95°F (+ 35°C)
Dimensions of the premises
For the mechanical dimensions of the cabinets, refer to the
“INSTALLATION DRAWINGS”
supplied with the
UPS and with the battery cabinet, if present. These drawings provide the following data:
the position of the holes in the base to secure the device to the floor, if applicable;
a view of the floor support for the sizing of a structure to raise the cabinet, if applicable;
the position of cable entry;
the position of the fans on the top of the UPS, for the positioning of a structure to convey the warm air
discharged by the equipment outside the premises, if applicable;
the input, output and battery cables section;
the power dissipated by the equipment (kW).