With the lever of SW1 in the start position in one UPS only and the lever in the cont position on all the others,
check that all the UPS’s are operating normally and that the system is sharing the output power.
Example of hot removal
With hot removal, it is not necessary to shut down all the UPSs of the system in order to remove one.
A) UPS parallel cable type
RJ45
B) RJ45 female/RJ45 female
shielded adaptor cable
UPS
BYPASS CABLE
NOTE: if the UPS to be
removed has SW1 in the start
position, one of the other
UPS’s (UPS 1 or UPS2) must
be in the start position.
One UPS in the system must
have SW1 in the start
position and LED ON.
I - Shut down the UPS (3) that
is to be removed. Remove the
signal cables of the UPS to be
removed.
II, III - Connect the RJ45
female/RJ45 female shielded
adaptor cable (not provided)
between cables A.
Check that all the UPS are operating normally and that the system is sharing the output power.
UPS 3
A
UPS 1
A
UPS 2
A
I
II
III
B
UPS 1
UPS 2
UPS 3
UPS 1
UPS 2