UPS models
160kVA
200kVA
250kVA
INTERMEDIATE D.C. CIRCUIT
N. cells (Lead acid batteries) [N]
Rated battery voltage [V]
240 (40 12Vdc battery)
480
Float charge (20°C) with cyclical charge
not active **
Battery type 1 or 2 [V]
3 [V]
0 [V]
542 (2,26V/cells-default)
528 (2,2 V/cells-default)
2÷2,5 V/cells programmable
Boost charge **
Battery type 1 or 2 [V]
3 [V]
0
[V]
562 (2,34 V/cells - default)
576 (2,40 V/cells - default)
2÷2,5 V/cells programmable
End of discharge (20°C) **
Battery type 1- 2-3 [V]
0 [V]
For Ibatt = 0÷Ah rated value 432÷395
For Ibatt>Ah rated value 384
375÷456 programmable
Max Vdc
[V]
600
Ripple voltage with recharged battery
[%]
~ 0
Max recharge current
[A]
Full load
35
45
55
Load 90%
60
80
100
Load 80%
90
110
140
Load
≤ 70%
110
130
165
** See 1.7 and 1.14.5