page 24 / 85 0MLMHTM16RUENUB
4.3
External Overcurrent Protection device and terminals
CAUTION
to reduce the risk of fire, connect only to a circuit provided with branch circuit
protection with maximum current rating per the table, below, in accordance with the National
Electrical Code, ANSI/NFPA 70.
Input (for single input unit)
UPS
models
Nominal
Current
Maximum
Current
OCP Current
OCP Device
rating
Bolt Size (in.)
160 kVA
188A
212A
265A
300A
3/8
200 kVA
235A
265A
331A
350A
3/8
250 kVA
294A
331A
414A
450A
3/8
OCP= Over Current Protection Device, must be rated for branch circuit protection.
Rectifier Input (for dual input unit)
UPS
models
Nominal
Current
Maximum
Current
OCP Current
OCP Device
rating
Bolt Size (in)
160 kVA
188A
212A
265A
300A
3/8
200 kVA
235A
265A
331A
350A
3/8
250 kVA
294A
331A
414A
450A
3/8
Bypass Input (for dual input unit)
UPS
models
Nominal Current
OCP Current
OCP Device rating
Bolt Size (in)
160 kVA
192A
240A
250A
3/8
200 kVA
241A
301A
325A
3/8
250 kVA
301A
376A
400A
3/8
Output
UPS
models
Nominal Current
Bolt Size (in)
160 kVA
192A
3/8
200 kVA
241A
3/8
250 kVA
301A
3/8
CAUTION
Output circuit protection requirement is determined by distribution circuit. Smaller wire
may be used for load wiring if rated load current is not needed and the appropriate circuit protection is
applied. Output circuit protection must be provided as a part of the installation.