3.1.6 Backfeed protection
The MASTER HE is provided with a device to prevent voltage backfeed on the input line due to an internal fault.
This protection device works by switching off the inverter if the current flow is faulty, thereby causing voltage
backfeed on the bypass line during operation from the inverter. If the fault occurs when the UPS is operating from
the battery, the load will not be powered.
Should it be required to avoid the shutting down of the inverter in order to keep the load powered by the inverter
even in the event of a double fault, the system can be customized to control the opening coil of a switch located
upstream by reprogramming one of the relays on the “REMOTE COMMANDS AND ALARMS” card.
The control logic allows the function of the relay to be reconfigured, for example for the backfeed alarm, and then
the free voltage contact can be used to control the triggering of a switch located on the UPS input.
3.1.7 Emergency power off device (EPO)
The UPS is pre-set to be connected to a remote emergency power off device as laid down in standard EN 62040-1-2.
If the remote device (not supplied with the equipment) is activated, the inverter output voltage is cut.
The connection procedure is shown below.
a - EPO terminal board located on the UPS
b - EPO switch (not provided).
On the MASTER HE , the jumper on the EPO terminals (page 19) must be removed, and the wires from the auxiliary
contact of the button must be connected in place of the jumper.
The contact must be closed with the button in the rest position and must open when the button is pressed.
UPS
a
b
Summary of Contents for MASTER HE
Page 2: ...pag 2 57 0MNMHEM30RUENUB 00 RPS SpA Viale Europa 7 37045 Legnago VR Italy www riello ups com ...
Page 6: ...pag 6 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...
Page 25: ...0MNMHEM30RUENUB 00 pag 25 57 This page is left blank intentionally ...
Page 35: ...0MNMHEM30RUENUB 00 pag 35 57 This page is left blank intentionally ...
Page 50: ...pag 50 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...
Page 52: ...pag 52 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...