pag. 34 / 57 0MNMHEM30RUENUB 00
INVERTER
This is the output stage, the function of which is to convert the direct voltage from the RECTIFIER or from the
BATTERY into stabilized sinusoidal alternating voltage. The inverter output is isolated from the input and from the
batteries by a galvanic isolation transformer.The inverter is always working, since the load connected to the UPS
output is always powered by the INVERTER (in NORMAL OPERATION)
STATIC SWITCH
This device allows the synchronized switch, automatic or manual, and in zero time, of the power supply to the load
from a protected line (inverter output) to an unprotected line ( bypass line) or vice versa.
The MASTER HE is provided with a device to prevent the backfeed of voltage to the input line after an internal
fault, known as “
BACKFEED PROTECTION”.
MANUAL MAINTENANCE BYPASS (SWMB )
This is a maintenance disconnector. The UPS can be excluded by closing SWMB and opening the other
disconnectors SWIN, SWBY, SWOUT while keeping the load on the output powered. This operation is necessary
when maintenance operations must be carried out inside the equipment without interrupting the power supply to the
load.
The disconnector is sized for the rated power of the UPS.
Summary of Contents for MASTER HE
Page 2: ...pag 2 57 0MNMHEM30RUENUB 00 RPS SpA Viale Europa 7 37045 Legnago VR Italy www riello ups com ...
Page 6: ...pag 6 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...
Page 25: ...0MNMHEM30RUENUB 00 pag 25 57 This page is left blank intentionally ...
Page 35: ...0MNMHEM30RUENUB 00 pag 35 57 This page is left blank intentionally ...
Page 50: ...pag 50 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...
Page 52: ...pag 52 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...