0MNMHEM30RUENUB 00 pag. 29 / 57
3.5.3 Standby-off (with mains present the load is not powered)
load not powered, in the event of an input mains failure the load is powered from the
inverter using the energy stored by the batteries.
Standby-Off:
if there is a mains power supply, UPS output is zero. The RECTIFIER remains on and keeps
the battery charged. The output voltage is only present when the mains power supply fails. The
system remains with output voltage = 0V while the voltage and the input frequency are within
the acceptance field. When the power supply line is restored, the UPS is automatically
repositioned in
Standby-Off
mode.
The letter
F
will be displayed on the second line of the BASIC MENU, near the UPS model.
3.5.4 Stabilizer (operation in on-line mode without battery)
load powered from the inverter, if there is a mains failure the load is not powered, the
batteries are not present.
Stabilizer:
The load is always powered through the inverter, with stabilized voltage and frequency,
using the energy from the input mains. The batteries are not present. In the event of an
input mains failure, the output of the STABILIZER is not powered.
The letter
S
is displayed on the second line of the BASIC MENU, near the UPS model.
3.5.5 Frequency converter (from 50 to 60Hz or vice versa)
load powered from the inverter with output frequency different from the input frequency; in
the event of an input mains failure the load may be powered from the inverter using the
energy stored by the batteries, if present.
Frequency converter:
MAINS present, load powered. The load is always powered through the inverter, with
stabilized voltage and frequency, using the energy from the input mains. The bypass line
is disabled and must not be connected (the connections between the main supply line and
the bypass line on the input bars must be removed).
SWMB
Do not use disconnector SWMB when the UPS is configured as a Frequency Converter.
N.B.
: the disconnector can be padlocked in order to ensure that it is not used.
Summary of Contents for MASTER HE
Page 2: ...pag 2 57 0MNMHEM30RUENUB 00 RPS SpA Viale Europa 7 37045 Legnago VR Italy www riello ups com ...
Page 6: ...pag 6 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...
Page 25: ...0MNMHEM30RUENUB 00 pag 25 57 This page is left blank intentionally ...
Page 35: ...0MNMHEM30RUENUB 00 pag 35 57 This page is left blank intentionally ...
Page 50: ...pag 50 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...
Page 52: ...pag 52 57 0MNMHEM30RUENUB 00 This page is left blank intentionally ...