- 32 -
PROBLEM
POSSIBLE CAUSE
SOLUTION
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F34, L34
AMBIENT
TEMPERATURE
HIGHER THAN 40°C
HEAT SOURCES CLOSE
TO THE CPS
VENTILATION SLITS
OBSTRUCTED OR TOO
CLOSE TO THE WALLS
Activate the maintenance bypass (SWMB) if present,
without switching off the CPS. This way, the fans will cool
the heat sink more rapidly. Eliminate the cause of the
overtemperature and wait for the temperature of the heat
sink to drop. Exclude the maintenance bypass.
FAULT IN TEMPERATURE
PROBE OR CPS COOLING
SYSTEM
Insert the maintenance bypass (SWMB) if present, without
switching off the CPS, so that the fans, while keeping
running, cool the heat sink more rapidly and wait for the
temperature of the heat sink to drop. Turn the CPS off and
back on again. Exclude the maintenance bypass and if the
problem persists, contact the nearest service centre.
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F37, L37
AMBIENT
TEMPERATURE
HIGHER THAN 40°C
HEAT SOURCES CLOSE
TO THE CPS
VENTILATION SLITS
OBSTRUCTED OR TOO
CLOSE TO THE WALLS
FAULT IN THE
TEMPERATURE PROBE
OR IN THE BATTERY
CHARGER COOLING
SYSTEM
Eliminate the cause of the overtemperature.
Activate the maintenance bypass (SWMB) if present, open
the battery fuse holder isolators (SWBATT) and wait for the
temperature of the battery charger heat sink to drop.
Close the battery fuse holders. If the problem persists,
contact the nearest service centre. WARNING: never open
the SWBATT fuse holder isolators during battery operation.
THE DISPLAY SHOWS
THE FOLLOWING CODE:
L11
STATIC BYPASS RUPTURE
OR FAULT
Activate the maintenance bypass (SWMB) if present. Turn
the CPS off and back on again. Exclude the maintenance
bypass and if the problem persists, contact the nearest
service centre.
THE DISPLAY SHOWS
NOTHING OR PROVIDES
INCORRECT
INFORMATION
THE DISPLAY HAS POWER
SUPPLY PROBLEMS
Activate the maintenance bypass (SWMB), shut down the
CPS completely and wait for a few seconds. Turn ON the
CPS again and verify display regular operation. Exclude
the maintenance bypass. If the fault persists, contact the
nearest technical support centre.
THE DISPLAY IS OFF,
THE FANS ARE OFF BUT
THE LOAD IS POWERED
FAULT IN THE AUXILIARY
POWER SUPPLIES.
THE CPS IS IN BYPASS
SUPPORTED BY THE
REDUNANT POWER
SUPPLY.
Activate the maintenance bypass (SWMB) if present.
Switch off the CPS, wait for a minute and turn the CPS
back on. If the display does not turn on or if the sequence
fails, contact the nearest service centre, leaving the CPS
in manual bypass mode.
THE DISPLAY SHOWS
THE FOLLOWING CODE:
ddp
THE CPS HAS REACHED
THE MINIMUM BATTERY
VOLTAGE LEVEL DURING
THE LAST MAINS FAILURE
The alert message can be removed only when the system
has returned to work correctly from the mains (as required
by the EN50171 standard). To remove the alert message,
press the ON key.
(*)
The alarm may occur the first time the CPS is switched on if the battery is incorrectly connected.
ATTENTION:
The CPS in case of a permanent failure will be not able to supply the load. To ensure total protection of your
equipment we suggest you install an ATS device (Automatic Transfer Switch) or an external automatic by-
pass. For more information visit
www.riello-ups.com