NORMAL OPERATION / FLAME SENSOR TIMING

The control box has a further function by means of which it is possible to check the correct running of the burner  (signal: 

GREEN LED

permanently lit up).
In order to use this function, it is necessary to wait at least ten seconds from the firing up of the burner and press the button of the control box for
a minimum of three seconds. 
Once the button has been released, the GREEN LED will start to flash, as illustrated in the diagram below.

The pulses of the LED constitute a signal spaced by approximately 3 seconds. 
The number of pulses will identify the SENSOR TIMING o f the probe from opening of the gas valve, according to the table below.

FONCTIONNEMENT NORMAL/ TEMPS DE RÉVÉLATION FLAMME

La boîte de contrôle a une autre fonction qui permet de contrôler si le brûleur fonctionne correctement (signalisation:

 LED VERT 

tou-

jours allumé).
Pour utiliser cette fonction, il faut attendre au moins dix secondes après l'allumage du brûleur et appuyer sur le bouton de la boîte pendant au
moins trois secondes.
Après avoir relâché le bouton, le LED VERT se met à clignoter comme indiqué sur la figure suivante.

Les impulsions du LED constituent un signal espacé d'environ 3 secondes.
Le nombre d'impulsions indique le TEMPS DE RÉVÉLATION de la sonde dès l'ouverture des vannes gaz, comme d'après le tableau suivant.

.

SIGNAL

FLAME SENSOR TIMING

Each time the burner is started up, this information is up-
dated
Once the reading has been taken, by pressing the button 
on the control box briefly, the burner repeats the start 
cycle.

WARNING

If a timing of > 2 seconds occurs, delayed start-up is 
present.
Check the setting of the hydraulic brake in the gas valve 
and the setting of the air gate valve and the combustion 
head.

1 flash

0.4 secs

2 flashes

0.8 secs

6 flashes

2.8 secs

SIGNAL

TEMPS DE REVELATION FLAMME

Cette donnée est mise à jour à chaque démarrage du 
brûleur.
Après avoir procédé à la lecture, il suffit d'appuyer 
brièvement sur le bouton de la boîte de contrôle pour que 
le brûleur répète le cycle de démarrage.

ATTENTION

L'allumage est retardé si le temps est >2 s.

 

Contrôler le 

réglage du frein hydraulique sur la vanne gaz ainsi que le 
réglage du volet d'air et de la tête de combustion.

1 clignotement

0.4 s

2 clignotements

0.8 s

6 clignotements

2.8 s

GB

GREEN LED on

wait at least 10 secs

Press button

for > 3 secs

Signal

Signal

Interval

3 secs

F

VOYANT VERT allumé

attendre au moins 10s

Appuyer sur le bouton

pendant > 3s

signal

signal

Intervalle

3s

Summary of Contents for 3866207

Page 1: ...Gebl se Gasbrenner Blown type gas burners Br leurs gaz air souffl 2916149 0 CODE MODELE MODEL TYPE 3866207 RS 68 M BLU 846 T 3866208 RS 68 M BLU 846 T 3866209 RS 120 M BLU 847 T I D GB F Funzionamento...

Page 2: ...erma en bezeichnet 1 A Detail 1 der Zeichnung A auf der gleichen Textseite 1 A S 8 Detail 1 der Zeichnung A auf Seite 8 D CONTENTS TECHNICAL DATA page 6 Variants 6 Accessories 6 Burner description 9 P...

Page 3: ...re calorifico inferiore kWh Nm3 Mcal Nm3 10 8 6 8 6 7 4 10 8 6 8 6 7 4 Densit assoluta kg Nm3 0 71 0 78 0 71 0 78 Portata massima Nm3 h 86 100 130 151 Pressione alla portata massima 2 mbar 11 7 17 3 2...

Page 4: ...8 6 8 6 7 4 10 8 6 8 6 7 4 Reindichte kg Nm3 0 71 0 78 0 71 0 78 H chstdruchsatz Nm3 h 86 100 130 151 Druck bei H chstleistung 2 mbar 11 7 17 3 22 5 33 3 BETRIEB Intermittierend min 1 Abschaltung in...

Page 5: ...orific value kWh Nm3 Mcal Nm3 10 8 6 8 6 7 4 10 8 6 8 6 7 4 Absolute density kg Nm3 0 71 0 78 0 71 0 78 Max delivery Nm3 h 86 100 130 151 Pressure at max delivery 2 mbar 11 7 17 3 22 5 33 3 OPERATION...

Page 6: ...G20 G25 Pouvoir calorifique inf rieur kWh Nm3 Mcal Nm3 10 8 6 8 6 7 4 10 8 6 8 6 7 4 Densit absolue kg Nm3 0 71 0 78 0 71 0 78 D bit maximum Nm3 h 86 100 130 151 Pression au d bit max 2 mbar 11 7 17...

Page 7: ...isco di stabilit fiamma 26 Staffa per l applicazione del regolatore di potenza RWF40 27 Prese per il collegamento elettrico Vi sono due possibilit di blocco del bruciatore BLOCCO APPARECCHIATURA l acc...

Page 8: ...to fan 21 Screws securing fan to sleeve 22 Gas input pipework 23 Gas butterfly valve 24 Boiler mounting flange 25 Flame stability disk 26 Bracket for mounting the power regulator RWF40 27 Socket for...

Page 9: ...a su caldaie con camera di combustione a deflusso dal fondo tre giri di fumo sulle quali si ottengono i migliori risultati di basse emissioni di NOx Lo spessore massimo del portello anteriore della ca...

Page 10: ...are suitable for operation on either flame inversion boilers or boilers with combustion chambers fea turing flow from the base three flue passes on which the best results are obtained in terms of low...

Page 11: ...ria alla presa 1 B fissata la potenza alla quale si desidera funzioni il bruciatore in 2 stadio Trovare nella tabella relativa al bruciatore considerato il valore di potenza pi vicino al valore deside...

Page 12: ...on the left Example RS 68 M BLU 2nd stage operation Natural gas G 20 PCI 10 kWh Nm3 Gas ring 2 B p 16 adjusted as indicated in diagram C p 16 Gas pressure at test point 1 B 11 6 mbar Pressure in comb...

Page 13: ...tore graduato 8 Togliere le viti 2 dalle due guide 5 Togliere le due viti 4 ed arretrare il bruciatore sulle guide 5 per circa 100 mm Disinserire i cavi di sonda ed elettrodo e quindi sfilare del tutt...

Page 14: ...sen the four screws 3 and remove the cover 1 Disengage the articulated coupling 7 from the graduated sector 8 Remove the screws 2 from the two slide bars 5 Remove the two screws 4 and pull the burner...

Page 15: ...a ghiera 2 B si ottengono ridu zioni sulla formazione di NOx Continuando l esempio precedente a pag 12 si vede che per un bruciatore RS 68 M BLU con potenza di 500 kW occorrono 5 0 mbar di pres sione...

Page 16: ...ram C indicates an optimal regulation for a type of boiler seen in fig B page 10 If the pressure of gas allows it by closing ring nut 2 B a reduction of the formation of NOx is obtained Continuing wit...

Page 17: ...cura dell installatore LEGENDA TABELLA C C T Dispositivo controllo tenuta valvole gas 8 9 Rampa priva del dispositivo di con trollo tenuta dispositivo che pu essere ordinato a parte vedi colonna 13 e...

Page 18: ...0 Standard issue burner gasket with flange 11 Gas adjustment butterfly valve 12 Burner 13 Gas valve 8 9 leak detection control device In accordance with EN 676 Standards gas valve leak detection contr...

Page 19: ...elettrica MB Morsettiera bruciatore MV Motore ventilatore PA Pressostato aria PGM Pressostato gas di massima RT Rel termico S1 Interruttore per funzionamento MAN manuale AUT automatico OFF spento S2...

Page 20: ...ell KEY TO LAYOUT A CMV Motor contactor F1 Protection against radio interfer ence LMG22 Control box MB Burner terminal strip MV Fan motor PA Air pressure switch PGM Maximum gas pressure switch RT Ther...

Page 21: ...bruciatore MB Morsettiera bruciatore XP Spina per controllo di tenuta X4 Spina a 4 poli X6 Spina a 6 poli X7 Spina a 7 poli PG Pressostato gas di min PS Pulsante di sblocco S Segnalazione di blocco a...

Page 22: ...ak detection con trol device Gas valve leak detection control takes place immediately before every burner start up Fuses layouts B and C see table D Cross section when not indicated 1 5 mm2 KEY TO LAY...

Page 23: ...co non comprende l assorbimento di targa del motore a 400 V la protezione assicurata lo stesso Nota I modelli RS 68 120 M BLU lasciano la fabbrica previsti per alimentazione elettrica 400 V Se l ali m...

Page 24: ...MIN If the motor is delta powered 230 V the cursor should be positioned to MAX Even if the scale of the thermal cut out does not include rated motor absorption at 400 V protec tion is still ensured i...

Page 25: ...ciatore funzionante alla potenza MAX la farfalla del gas deve risultare tutta aperta 90 Camma I I 0 Limita la rotazione verso il minimo A bruciatore spento la serranda dell aria e la far falla del ga...

Page 26: ...m and the gas butterfly valve It rotates through 130 degrees in 33 seconds Do not alter the factory setting for the 5 cams simply check that they are set as indicated below Cam I 130 Limits rotation t...

Page 27: ...ll accensione deve essere uguale o inferiore a 300 kW con ts 2 s 200 kW con ts 3 s Per misurare la potenza all accensione scollegare la spina presa 7 A p 8 sul cavo della sonda di ionizzazione il bruc...

Page 28: ...ner will fire and then go into lock out after the safety time has elapsed Perform 10 firings with consecutive lock outs On the meter read the quantity of gas burned This quantity must be equal to or l...

Page 29: ...e che la variazione del profilo della camma sia progressiva Spegnere il bruciatore agendo sull interruttore 1 A p 28 posizione OFF svincolare la camma 4 A dal servomotore premendo e spostando verso de...

Page 30: ...nfin reporter le servomoteur en position de puis sance MIN avec le bouton diminution de la puissance Pour le r glage ventuel de la came I I I surtout pour de l gers d placements on peut utiliser la cl...

Page 31: ...ssima dopo aver effettuato tutte le altre rego lazioni del bruciatore con il pressostato gas di massima regolato a fine scala B Con il bruciatore funzionante alla potenza mas sima diminuire la pressio...

Page 32: ...burner adjustments with the maximum gas pressure switch set to the end of the scale B With the burner operating at MAX output reduce the adjustment pressure by slowly turn ing the adjustment knob anti...

Page 33: ...re la presenza della fiamma e la corretta posizione del pressostato aria Se la temperatura o la pressione bassa per cui il telecomando TR chiuso il bruciatore aumenta progressivamente la potenza fino...

Page 34: ...continue cependant contr ler la pr sence de la flamme et la bonne position du pressostat de l air Si la temp rature ou la pression sont basses et que par cons quent la t l commande TR est ferm e le br...

Page 35: ...sante 2 B p 30 Bruciatore Controllare che non vi siano usure anomale o viti allentate nei cinematismi che comandano la serranda aria e la farfalla del gas Cos pure bloccate devono essere le viti che f...

Page 36: ...by moving the but ton 2 B p 30 to the left Burner Check for excess wear or loose screws in the mechanisms controlling the air gate valve and the gas butterfly valve Also make sure that the screws secu...

Page 37: ...atore si avvia ma si arresta in blocco 17 Presenza di fiamma durante la preventilazione Verificare tenuta valvola 18 Guasto all apparecchiatura elettrica Sostituire apparecchiatura 7 lampeggi Il bruci...

Page 38: ...ab schaltung an 17 Flamme bei Vorbel ftung vorhanden Dichtheit des Ventils berpr fen 18 Defekt am Steuerger t Ger t austauschen 7 maliges Blinken Der Brenner geht gleich nach der Flam menbildung in St...

Page 39: ...replace it 5 flashes The burner starts up but halts in lock out 17 Flame presence during pre purging Check the valve tightness 18 Fault on electric control box Replace control box 7 flashes The burner...

Page 40: ...lamme durant la pr ventilation Contr ler l tanch it de la vanne 18 Panne de la bo te lectrique Remplacer la bo te lectrique 7 clignotements Le br leur se bloque juste apr s l appari tion de la flamme...

Page 41: ...nden Abbildung gezeigt Die Impulse der LED verursachen ein Signal das ca alle 3 Sekunden gegeben wird Die Anzahl der Impulse wird die Zeit festlegen die der F hler ab ffnung der Gasventile f r die Wah...

Page 42: ...e Les impulsions du LED constituent un signal espac d environ 3 secondes Le nombre d impulsions indique le TEMPS DE R V LATION de la sonde d s l ouverture des vannes gaz comme d apr s le tableau suiva...

Reviews: