7.3 Check: Control direction of the Manual Control (MC)
1.
Use the manual control (MC). Let the motor gearbox turn in a direction that can cause no
damage to the operated system.
2.
Make sure that the symbols on the manual control (MC) agree with the necessary moving
direction (of the operated system).
Direction A
Direction B
CORRECT - Go to step 5.
NOT CORRECT - De-energize the system. Go to step 3.
3.
Interchange the connections 2 and 4 of connector X8.
4.
Energize the system. Go to step 1.
5.
The check procedure of the direction-of-rotation of the manual control is completed.
Installation cover
Always put the cover and the bolts (8x) back after the work.
Problems
with
moisture
and/or the
IP
protection rating (if applicable) must be
prevented!
•
Do a check of the gasket for dirt and damages.
•
Put the gasket (if removed) back carefully and make sure that no damage is caused.
•
Tighten the bolts crosswise and gradually with the correct tightening torque.
Control board A2
X8
Manual Control (MC)
1
24 V DC
2
Direction A
3
Auto
4
Direction B
5
LED red (D2)
6
LED green (D1)
HEX 4 mm (8x)
2 Nm
(maximum)
Ridder Drive Systems B.V.
T
+31 (0)341 416 854 -
F
+31 (0)341 416 611 -
I
26