22

2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 s. 
3 -  Press the remote control button (normally channel B) within the 10 s proscribed. If the 

remote control has been correctly programmed, the DL2 LED (green) will flash once.

4 -  The code programming time resets automatically so that you can programme the next 

remote control. 

5 -  To finish programming, let 10 s pass and then press the PROG. button briefly. The red DL1 

LED will stop flashing. 

6 -  Turn 

DIP 1 to OFF

 and 

DIP 3 to OFF

.

 N.B:  IF THE DL1 LED CONTINUES TO FLASH RAPIDLY, THIS MEANS THAT DIP 1 IS STILL POSITIONED 

TO ON AND ANY MANOEUVRE HAS BEEN DELETED. 

PROCEDURE FOR DELETING ALL RADIO CODES USED ONLY FOR COMPLETE OPENING 

You can only delete the codes if the gate is closed. 
1 -  Position 

DIP 1 to ON

 and then 

DIP 3 to ON

.

2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 s. 
3 -  Press and hold the PROG button for 5 s. The green DL2 LED will flash twice to confirm that 

the stored codes have been deleted. 

4 -  The red programming DL1 LED remains active and you can programme new codes as shown 

above if required. 

5 - Turn 

DIP 1 to OFF

 and 

DIP 3 to OFF

.

HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR COMPLETE OPENING 

You can only check the memory if the gate is closed. 
1 - Position 

DIP 1 to ON

 and then 

DIP 3 to ON

.

2 -  The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored). 
3 -  After this, the DL1 programming LED will remain active for 10 s, so that you can delete all 

codes if required. 

4 - Turn 

DIP 1 to OFF

 and 

DIP 3 to OFF

.

FUNCTIONING OF CONTROL ACCESSORIES

ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors) used on 
the installation are set in the IMPULSIVE mode, otherwise, the gate will be operated even 
without the protection of the safety devices.

STEP BY STEP or AUTOMATIC commands  
(K BUTT button,  PED BUTT button, RADIO REMOTE button)
DIP 6 - ON

  The K BUTT,  the PED BUTT button, the RADIO REMOTE buttons perform the cyclic 

command open-stop-close-open-stop-etc.

DIP 6 - OFF

  The K BUTT,  the PED BUTT button, the RADIO REMOTE buttons perform:

 

 -  the open command, if pressed with the gate completely closed

 

 -  the close command, if pressed with the gate completely opened

 

- no effect, if pressed during the gate opening  

 

- the gate re-open, if pressed while the gate is closing

The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as 
described in Point D.

CLOCK FUNCTION

If you want the Clock Function must request K with firmware 12 NOUP.
ATTENTION: A CLOCK CONNECTED TO K with fw 05 or more ACTIVATES THE AUTOMATIC 
MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES!

The Clock Function is useful during rush hours, when traffic is heavy and the flow is slow (e.g. 
entrance/exit of employees, emergencies in residential areas or car parks and, temporarily, for 
removal vans) and it’s necessary to keep the gate opened.

CLOCK FUNCTION APPLICATION
It is necessary to request a K control panel with firmware 12 NOUP.

Select the automatic functioning 

DIP 6 OFF

.

It can be done by connecting a switch and/or a daily/weekly clock either in parallel to the K 
BUTT button or instead of the K BUTT button. When the control board receives this command, 
the gate will open and by 

keeping this contact closed for all the time of the gate opening, the 

Clock Function is automatically activated

. In fact, once reached the open position, the gate will 

remain opened and all of the control board functions are blocked. Only 

when K BUTT contact is 

released, the control board functions are re-activated

 and the Automatic Closing restarts (if 

enabled) doing the countdown to the gate closing.

PEDESTRIAN command (PED BUTT - COM)

This command is useful to open the gate partially, just enough, for example, to permit a 

pedestrian crossing. In fact, the Pedestrian command (see Point E) is carried out only by 
opening the gate just enough for a pedestrian to pass, as described into the Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or disabled with 

DIP 3

From the Pedestrian opening position, the gate can be completely opened by the OPEN or by the 
K BUTT button or by the RADIO button.

AUTOMATIC CLOSING (from the COMPLETE open position)

The Automatic Closing from the complete open position can be enabled turning 

DIP 3 to ON

.

The maximum gap of time that can be programmed is 5 minutes (see Point D).

AUTOMATIC CLOSING (from the PEDESTRIAN open position)

The Automatic Closing from the pedestrian open position can be enabled turning 

DIP 3 to ON

The maximum gap of time that can be programmed is 5 minutes (see Point E).

FUNCTIONING OF SAFETY ACCESSORIES

PHOTOCELL (PHOT - COM) - Safety function - PL ”b” according to EN13849-1
DIP 4 OFF

 => the photocells are 

active both in gate opening and in gate closing.

 In this 

configuration, if an obstacle cuts the photocell beam: 
- while the gate is closing, the gate will open
-  while the gate is opening, the gate will stop and will restart opening when the obstacle is 

removed

-  while the gate is still, it will not move neither in opening nor in closing.

DIP 4 ON

 => the photocells are 

active only in gate closing

In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
-  while the gate is still, it will open if a open command is request, it will remain still if a close 

command is request.

The photocell input (PHOT - COM) is a NORMALLY CLOSED contact. 
In case there are more couple of photocells, the contacts from all the photocell receivers must 
be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump 
(from PHOT to COM) to permit the gate to operate.

ATTENTION:  In case the receiver led remains lit, malfunctioning of the main supply is 

suspected. 

It is advisable to connect electrically to earth the columns 
or the photocells stands to the terminal A -, to shield the 
photocells from external noise.
Be careful not to short circuit the system when the supply 
phases are inverted!

SAFETY STRIP (EDGE - COM) - Safety function - PL ”b” according to EN13849-1

If it intervenes during opening, it inverts the movement and closes for 2 s and then stops.
If it intervenes during closing, it inverts the movement and opens for 2 s and then stops.
If the safety strip remains engaged (NO contact), no automatic movement is allowed.
In case the safety strip is not installed, this contact must be short circuited with a wire jump 
(from EDGE to COM) to permit the gate to operate.

PAY ATTENTION: it is highly recommended to check safety-strips operation at least every 6 
months.

SAFETY STRIP ALARM

After the inversion given by the intervention of the safety edge, the gate stops in alarm mode 
and this is signaled by the blinker on for 1 minute and by the buzzer on for 5 minutes.
During or after the minute of alarm, the normal gate operations can be restored by pressing 
any push button.

TESTING THE SAFETY STRIP equipment 
DIP 10 ON

 => enables to test the safety strip equipment. 

The test is performed every time the gate completes a full opening. The test is available 

only if 

the safety strip device is equipped with a dedicated power supply input.

In fact, the safety strip equipment power supply input can be connected to the A+TEST and 
A- outputs (

DIP 10 ON

). Automatically, every time the gate completes a full opening, just before 

closing, the control board switches OFF the A+TEST and A- power supply output for a very short 
time. While the safety strip power supply is switched OFF, if everything is working fine the 
safety strip contact (EDGE - COM) must open. In case the test fails, no other gate manoeuvre 
will be allowed and the alarm state will be signalled by both the Blinker and the Buzzer, if 
installed, which will remain on for 5 minutes

NOT ALL THE  SAFETY STRIPS CAN  BE TESTED, THUS THE SWITCH DIP 10 MUST BE LEFT OFF.

STOP BUTTON - Safety function - PL ”b” according to EN13849-1

G

B

24 Vdc

Term.

A -

Summary of Contents for K-CRX

Page 1: ...in the IMPULSIVE mode otherwise the gate will be operated even without the protection of the safety devices Arbeit im mannsbeisein im fall eines ausfalls der Sicherheiten In bereinstimmung mit der ak...

Page 2: ...ovocati dalla mancata osservanza nell installazione delle norme di sicurezza e delle leggi attualmente in vigore ATTENTION POUR LA SECURITE DES PERSONNES IL EST IMPORTANT DE SUIVRE TOUTES LES INSTRUCT...

Page 3: ...s caused by the non observance during the installation of the safety standards and of the laws in force at present ACHTUNG F R DIE SICHERHEIT DER PERSONEN IST ES WICHTIG DASS ALLE ANWEISUNGEN GENAU AU...

Page 4: ...dell acquisto di una nuova apparecchiatura di tipo equivalente Presso i distributori di prodotti elettronici con superficie di vendita di almeno 400 m2 inoltre possibile consegnare gratuitamente senz...

Page 5: ...Hz SAIL 230Vac 40 W max APRE ANTENNA COMUNE COMUNE PEDONALE PASSO PASSO BUZZER 24 Vdc 0 4A 15 24 Vdc 0 4A 15 LED R 2K2 COSTA MECCANICA FOTOCELLULE CHIUDE AUTOTEST PER COSTA ACCESSORI A COLLEGAMENTI EL...

Page 6: ...IOCOMANDOAPERTURATOTALE DIP 1 ON seguito da DIP 2 ON PUNTO E SOLO PER MODELLI CRX DIP 1 3 MEMORIZZAZIONE CANCELLAZIONE CODICI RADIO COMANDO APERTURA PEDONALE DIP 1 ON seguito da DIP 3 ON PUNTO F SOLO...

Page 7: ...la programmazione le funzioni di sicurezza Costa Fotocellule e Pulsante di stop sono attive La programmazione pu essere eseguita con il cancello in qualsiasi posizione 1 Mettete il DIP 2 su ON Il led...

Page 8: ...DIP 6 ON Esegue un comando ciclico dei comandi apre stop chiude stop apre etc DIP 6 OFF Esegue l apertura a cancello chiuso Se azionato durante il movimento di apertura non ha effetto Se azionato con...

Page 9: ...tivo LSC 3 W max Ha il compito di segnalare gli stati di cancello aperto parzialmente aperto o comunque non chiuso totalmente Solo a cancello completamente chiuso si spegne N B Collegare in serie al l...

Page 10: ...to con DIP 4 OFF Sistemare o sostituire il relativo contatto Azionando il pulsante K il cancello non esegue nessun movimento ImpulsoKsempreinserito Controllareesostituireeventualipulsantiomicro interr...

Page 11: ...Wi Fi locale WLAN APP8066 Modulo RJ45 per Scheda APP per gestire la centrale tramite rete dati locale LAN FIT SIX EN12978 EN13849 2 da incasso portata 15 30 m cod ACG8049 FIT SLIM EN12978 EN13849 2 FO...

Page 12: ...Vac 50 Hz SAIL 230Vac 40 W max OUVRE ANTENNE COMMUN COMMUN PIETON PAS A PAS BUZZER BARRE PALPEUSE PHOTOCELLULES FERME AUTOTEST POUR BARRE PALPEUSE ACCESSOIRES 24 Vdc 0 4A 15 24 Vdc 0 4A 15 A BRANCHEME...

Page 13: ...UVERTURE PIETONNE DIP 2 ON SUIVI DE DIP 1 ON POINT D DIP 1 2 MEMORISATION ANNULATIONCODESRADIOCOMMANDEOUVERTURETOTALE DIP1ONsuivi de DIP 2 ON POINT E UNIQUEMENT POUR MODELES CRX DIP 1 3 MEMORISATION A...

Page 14: ...arres palpeuses et les photocellules sont inactives D PROGRAMMATION TEMPS OUVERTURE TOTALE ATTENTION Si les entr es PHOT et EDGE ne sont pas raccord es faire des ponts entre COM PHOT et COM EDGE avant...

Page 15: ...l interrupteur ou lorsque l heure ins r e est chue on aura la fermeture imm diate de l automation BOUTON OUVERTURE PIETONNE COM PED BUTTON Commande d di e une ouverture partielle et la refermeture Du...

Page 16: ...U CLIGNOTANT N B Ce coffret lectronique NE PEUT ALIMENTER QUE DES FEUX CLIGNOTANTS AVEC CIRCUIT CLIGNOTANT ACG7072 avec lampe de 40 W maximum FONCTION PR CLIGNOTEMENT DIP 5 OFF le moteur le feu cligno...

Page 17: ...de contact chou v rifier les raccordements entre le tableau lectronique et l alimentateur des bandes de contact Attention si on n utilise pas un alimentateur pour bandes de contact le DIP10 doit tre s...

Page 18: ...FIT SLIM EN12978 EN13849 2 PHOTOCELLULES MURALES code ACG8032B PAIRE DE POTEAUX POUR FIT SLIM code ACG8065 Les photocellules FIT SLIM ont la fonction de synchronisme dans le courant C A et une gamme d...

Page 19: ...0Vac 50 Hz SAIL 230Vac 40 W max OPEN AERIAL COMMON COMMON PEDESTRIAN K BUTTON BUZZER EDGE PHOTOCELLS CLOSE FOR AUTOTEST STRIP FOR ACCESSORIES SUPPLY 24 Vdc 0 4A 15 24 Vdc 0 4A 15 POINT A ELECTRIC CONN...

Page 20: ...OINT F ONLY FOR CRX MODELS DIP 1 3 STORAGE DELETION OF RADIO CODES FOR PEDESTRIAN OPENING DIP 1 to ON followed by DIP 3 to ON POINT G ONLY FOR CRX MODELS OPERATING MODE SETTINGS DIP 3 ON Automatic Clo...

Page 21: ...control board Any changing of the safety devices input state will stop the procedure that must be repeated from the beginning 1 The gate must be fully closed 2 Turn DIP 2 to ON position LED DL1 start...

Page 22: ...d out only by opening the gate just enough for a pedestrian to pass as described into the Point E procedure From the Pedestrian opening position the Automatic Closing can be enabled or disabled with D...

Page 23: ...ng the alarm situations safety strip the buzzing will almost be constant GATE OPEN INDICATOR A negativo LSC 3 W max It is turned ON when the gate is open or partially open it is turned OFF only when t...

Page 24: ...the time set Ensure to have set DIP 3 to ON Button K BUTTON always inserted in automatic functioning mode DIP 6 OFF Replace button or switch of the selector switch Failed edge self test check the con...

Page 25: ...Wi Fi network WLAN APP8066 RJ45 module for APP card to manage the control panel using the local network LAN FIT SLIM EN12978 EN13849 2 PHOTOCELLS for the wall installation code ACG8032B PAIR OF COLUM...

Page 26: ...z SAIL 230Vac 40 W max FFNE ANTENNE ALLGEMEINE ALLGEMEINE FUSSG NGER SCHRITT BEI SCHRITT BUZZER MECHANISCHE RIPPE FOTOZELLEN SCHLIESSE AUTOTEST F R GELENKRIPPE ZUBEH RE 24 Vdc 0 4A 15 24 Vdc 0 4A 15 A...

Page 27: ...KT D DIP 1 2 SPEICHERUNG L SCHUNG FUNKCODES F R STEUERUNG GESAMT FFNUNG DIP 1 auf ON gefolgt von DIP 2 auf ON PUNKT E NUR F R DIE MODELLE CRX DIP 1 3 SPEICHERUNG L SCHUNG FUNKCODES STEUERUNG FUSSG NGE...

Page 28: ...EDGE ausf hren und zwar vor der Programmierungsprozedur Hinweis In diesem Fall sind die Sicherheitsfunktionen Kontaktleiste und Photozellen NICHT aktiv Hinweis W hrend der Programmierung sind die Sich...

Page 29: ...F Die ffnung bei geschlossenem Tor ausf hren Wenn w hrend der ffnungsbewegung in Betrieb gesetzt bleibt die Wirkung aus Wenn bei offenem Tor f r Fu g nger in Betrieb gesetzt wird sich dieses schlie en...

Page 30: ...Signalschwankung erh ht KONTROLLAMPE F R DIE SIGNALISIERUNG TOR OFFEN A negativo LSC 3 W max Diese Kontrolllampe ist daf r zust ndig die Position des offenen Tores zu signalisieren dies wenn dieses nu...

Page 31: ...ss DIP 3 auf ON gestellt ist Die K BUTTON Taste ist im Automatikbetriebsmodus stets eingeschaltet DIP 6 OFF Taste oder Switch des W hlers ersetzen Autotest Rippe gescheitert Verbindungen zwischen Scha...

Page 32: ...EN12978 EN13849 2 WANDFOTOZELLEN Kode ACG8032B EIN PAAR FOTOZELLEN STAENDER F R FIT SLIM Kode ACG8065 FIT SLIM Fotozellen haben Synchronismusfunktion im Wechselstrom Strom und Strecken 20 m Dank einer...

Page 33: ...230Vac 50 Hz SAIL 230Vac 40 W max ABRE ANTENA COM N COM N PEATONAL PASSO PASSO BUZZER COSTA MEC NICA FOTOC LULAS CIERRA AUTOTEST PARA BANDA ACCESORIOS 24 Vdc 0 4A 15 24 Vdc 0 4A 15 A CONEXIONES EL CT...

Page 34: ...N C DIGOS DE RADIO MANDO APERTURA TOTAL DIP 1 ON seguido de DIP 2 ON PUNTO E S LO PARA MODELOS CRX DIP 1 3 MEMORIZACI N CANCELACI N C DIGOS DE RADIO MANDO APERTURA PEATONAL DIP 1 ON seguido de DIP 3 O...

Page 35: ...er con la programaci n N B en este caso las funciones de seguridad de Bandas y Fotoc lulas NO est n activas N B Durante la programaci n las funciones de seguridad de Bandas Fotoc lulas y bot n de para...

Page 36: ...ible elegir la modalidad de funcionamiento del pulsador de mando peatonal DIP 6 ON Efect a un mando c clico de los comandos abre stop cierra stop etc DIP 6 OFF Efect a la abertura con la cancela cerra...

Page 37: ...ndos antes del motor BUZZER Opci n COM BUZZER Corriente disponible para el funcionamiento del buzzer 200 mA a 24 Vdc Durante la apertura y el cierre el buzzer emitir una se al sonora intermitente En c...

Page 38: ...habilitado en modalidad de funcionamiento autom tico DIP 6 OFF Sustituya pulsador o switch del selector Fallo Autotest borde verifique las conexiones entre el cuadro electr nico y alimentador para bor...

Page 39: ...local WLAN APP8066 M dulo RJ45 para Tarjeta APP para administrar el panel de control a trav s de una red local LAN FIT SLIM EN12978 EN13849 2 FOTOC LULAS PARA PARED c d ACG8032B PAR DE COLUMNAS PARA...

Page 40: ...35 UE und 2014 53 UE Alle grundlegenden Anforderungen gem Anhang I der Richtlinie UE 2006 42 CE angewendet wurden Die bereinstimmung mit den genannten harmonisierten Normen sieht die Vermutung der ber...

Reviews: