RHE26/27 Installation & Startup Guide – Doc. No. 8.2.1.06 – Ver. 1.40
25
Digital Input Configuration
To configure the digital inputs, navigate to
the menu item “HMI” under User Login
(Figure 19).
1.
Select “HMI” [H] and navigate to the “DI1
Property” (digital input 1) [H02] or to the
“DI2 Property” (digital input 2) [H03]
menu.
2.
Select one of the options stated in Table
11.
Table 5: Digital Input Setting Options
ID
Abbreviation
Full Name / Description
[H02]
[H03]
DI1Property
DI2Property
Property of Digital Input 1/2:
Functionality of Digital Input 1/2:
0: DI1/2 is disabled. All inputs are ignored (default).
1: DI1/2 causes the start of a Zeroing Process. Logic is positive – a transition to a high logic level
starts the Zeroing.
2: DI1/2 causes the start of a Zeroing Process. Logic is negative – a transition to a low logic level
starts the Zeroing.
3: DI1/2 causes reset of the Totalizers and the start of Batch Processing if configured, see RHE2X
Desktop Reference, Batch Mode. Logic is positive – a transition to a high logic level starts the
Batch.
4: DI1/2 causes reset of the Totalizers and the start of Batch Processing if configured, see RHE2X
Desktop Reference, Batch Mode. Logic is negative – a transition to a low logic level starts the
Batch.
5: A transition from low to high at DI1/2 stops the totalizers when they are in the running state. A
transition from high to low at DI1/2 restarts the totalizers when they are in the stopped state.
6: A transition from high to low at DI1/2 stops the totalizers when they are in the running state. A
transition from low to high at DI1/2 restarts the totalizers when they are in the stopped state.
Figure 19: RHE26/27 Menu – Digital Output Configuration