RHE26/27 Installation & Startup Guide – Doc. No. 8.2.1.06 – Ver. 1.40
10
3.2.1.4
Legacy RHM Sensors (9 Terminals)
Table 6: RHE26/27 Wiring Plan for RHM legacy version
RHM Terminal
Cable
RHE2x Terminal
No.
Wire Color
Function
No.
Name
1
Brown
Drive Coil high
1
DrvH
2
Blue
Drive Coil low
2
DrvL
3
Red
Temperature Sensor Pipe Supply
3
PtP
4
Pink
Temperature Sensor Pipe Sense
4
PtG
5
Orange
Temperature Sensors Common
5
PtT
6
Yellow
Pick Up Coil A high
6
PkAH
7
Green
Pick Up Coil A low
7
PkAL
8
Grey
Pick Up Coil B low
8
PkBL
9
White
Pick Up Coil B high
9
PkBH
Screw Term
1
(yel/grn)
Shield
10
PE
1
The shield of the cable is connected to the housing of the RHM using a screw terminal in the junction box. If there
is a risk of a significant potential difference between the housing of the RHM and the PE terminal of the RHE, the
shield should be connected to the RHE PE connection via a 1nF capacitor. Alternatively, a separate cable can be run
for potential equalization between the RHM case and the RHE and the shield left both unconnected and isolated at
the RHE or terminated to the PE connection via a 1nF capacitor.
Upon power up, if the RHE indicates an error and the temperature measurement on the bottom
right of the display shows “ -.--°C/°F ” please check the temperature measurement configuration
setting in the RHE (section 4.5).
The correct temperature measurement configuration setting for an RHM legacy sensor is “1”.
Figure 4: RHE26/27 Wiring with RHM legacy sensors
RHM RHE26/27