Status LED
Status LED Description
Status LED Troubleshooting Information
Green “POWER”
Module has power
Supply voltage is present at module terminals
Red “TRIP”
Thermostat demand signal
1. Compressor internal overload is open
Y1 is present, but the
2. Broken wire or connector is not making contact
compressor is not
3. Low pressure switch open, if present
running
4. Compressor contactor has failed
Yellow “ALERT”
A. Low refrigerant charge
B. Evaportaor blower is not running
C. Evaporator coil is frozen
D. Faulty TXV
E. Condenser coil is dirty
F. Liquid line restriction (filter drier blocked, if present in system)
G. Thermostat is malfunctioning
A. Low refrigerant charge
B. Evaportaor blower is not running
C. Evaporator coil is frozen
D. Faulty TXV
E. Condenser coil is dirty
F. Liquid line restriction (filter drier blocked, if present in system)
G. Thermostat is malfunctioning
LED on Solid
A short circuit or
over-current condition exists
on "P" terminal
Yellow “ALERT”
System Pressure Trip
1.
Flash Code 2
Discharge or suction
2.
Condenser coil poor air circulation (dirty, blocked, damaged)
pressure out of limits or
3.
Condenser fan is not running
compressor overloaded
Return
4. If low pressure switch is present:
air duct has substantial leakage
Yellow “ALERT”
Short Cycling
1.
Thermostat demand signal is intermittent
Flash Code 3
Compressor is running
2.
T ime delay relay defective, if present
only briefly
3.
4.
Yellow “ALERT”
Locked Rotor
1.
Flash Code 4
2.
Low line voltage (contact utility if voltage at disconnect is low)
3.
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Hot gas sensor defective, if present
Yellow “ALERT”
Open Circuit
1.
Flash Code 5
2.
3.
Compressor contactor has failed open
4.
High pressure switch is open, if present
5.
Open circuit in compressor supply wiring or connections
Unusually long compressor protector reset time due to
extreme ambient temperature
Compressor windings are damaged
Yellow “ALERT”
Missing Phase
1. Broken wire or connector on one phase
Flash Code 6
"Lockout"
"Lockout"
"Lockout"
2. Compressor motor winding is damaged
3. Utility supply has dropped one phase
Yellow “ALERT”
Reverse Phase
1. Compressor running backwards due to supply phase reversal
Flash Code 7
"Lockout"
"Lockout"
Yellow “ALERT”
Welded Contactor
1. Compressor contactor has failed closed
Flash Code 8
Compressor always runs
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Low Voltage
1. Control circuit transformer is overloaded
Flash Code 9
Control circuit < 18VAC
2. Low line voltage (contact utility if voltage at disconnect is low)
• Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated.
• TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.
• Reset ALERT Flash code by removing 24VAC power from module.
• Last ALERT Flash code is displayed for 1 minute after module is powered on.
92-101534-04-00
High head pressure
3 PHASE UNIT
3 PHASE UNIT
Summary of Contents for RRNL
Page 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 40: ...40 FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 80: ...80 FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS...
Page 81: ...81 FIGURE 36 WIRING DIAGRAM...
Page 82: ...82 FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL...
Page 83: ...83 FIGURE 38 WIRING DIAGRAM...
Page 84: ...84 FIGURE 39 WIRING DIAGRAM...
Page 85: ...85 FIGURE 40 WIRING DIAGRAM...
Page 86: ...86 FIGURE 41 WIRING DIAGRAM...
Page 87: ...87 FIGURE 42 WIRING DIAGRAM...
Page 88: ...88 FIGURE 43 WIRING DIAGRAM...
Page 91: ...91 FIGURE 46 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 93: ...93 FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 106: ...106 15 SECOND PREPURGE FIGURE 61...