E. COOLING AIRFLOW ADJUSTMENTS
Cooling airflow may be ad10% or –10% from nominal airflow using switches 3 & 4.
Refer to Figure 33 for switch positions to achieve the desired adjustments in airflow.
NOTE:
Continuous fan speed is NOT affected by switches 3 & 4.
IMPORTANT:
The use of On Demand Dehumidification overrides the cooling airflow adjust-
ments when high humidity is detected by a dehumidifying thermostat or humidistat when con-
nected to the ODD terminal as shown in Figure 28. Refer to the Cooling Mode
Dehumidification section for more information.
FIGURE 30
COOLING AIRFLOW ADJUSTMENTS
COOLING
SELECTION
SWITCH 3
SWITCH 4
AIRFLOW
POSITION
POSITION
ADJUSTMENT
A
OFF
OFF
NONE
B
ON
OFF
10%
C
OFF
ON
-10%
D
ON
ON
NONE
O
N
O
N
O
N
O
N
A
3
4
3
4
3
4
3
4
B
C
D
Summary of Contents for RRNL
Page 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 40: ...40 FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 80: ...80 FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS...
Page 81: ...81 FIGURE 36 WIRING DIAGRAM...
Page 82: ...82 FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL...
Page 83: ...83 FIGURE 38 WIRING DIAGRAM...
Page 84: ...84 FIGURE 39 WIRING DIAGRAM...
Page 85: ...85 FIGURE 40 WIRING DIAGRAM...
Page 86: ...86 FIGURE 41 WIRING DIAGRAM...
Page 87: ...87 FIGURE 42 WIRING DIAGRAM...
Page 88: ...88 FIGURE 43 WIRING DIAGRAM...
Page 91: ...91 FIGURE 46 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 93: ...93 FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 106: ...106 15 SECOND PREPURGE FIGURE 61...