Selection B:
Factory Setting
This is the factory setting and provides cooling airflows as defined in the COOLING AIR-
FLOWS section (no reduction in airflow).
Selection C:
On Demand Dehumidification
This selection allows On Demand Dehumidification when using a dehumidifying thermo-
stat or humidistat connected to the ODD and “R” pigtails. Nominal airflow is reduced by a
preprogrammed amount to maximize latent removal. When high humidity is detected, the
cooling airflow as shown in Table 12.
IMPORTANT:
A humidistat or dehumidifying thermostat MUST be connected to the “ODD”
and “R” pigtails when using this setting. Refer to the explanation of On Demand
Dehumidification use for more information.
Selection D:
No Adjustment
This selection is the same as the factory setting and provides cooling airflows as defined in
the NOMINAL AIRFLOW ADJUSTMENT section.
ON DEMAND DEHUMIDIFICATION INTERACTIONS WITH AIRFLOW
ADJUSTMENT SETTINGS
On Demand Dehumidification switch settings (9 & 10) override the cooling airflow adjustment
switch settings (3 & 4). The +/-10% adjustments are turned OFF when Selection A (switch 9 &
10 are OFF) or Selection C (switch 9 OFF; switch 10 ON and no signal to ODD terminal) is
used.
43
TABLE 11
MODEL
SWITCH
SWITCH
Y1
Y2
9 POSITION
10 POSITION
CFM
CFM
RRRL-B024
OFF
OFF
468
680
RRRL-B036
OFF
OFF
680
1020
RRRL-B048
OFF
OFF
893
1360
RRRL-B060
OFF
OFF
1063 1573
TABLE 12
RRRL-
SWITCH 9
POSITION
SWITCH
10
POSITION
ODD
INPUT
Y1
CFM
Y2
CFM
B024
B036
B048
OFF
OFF
OFF
ON
ON
ON
NONE
24VAC
468
550
680
800
NONE
24VAC
680
800
1020
1200
NONE
24VAC
893
1050
1360
1600
B060
OFF
ON
NONE
24VAC
1063
1250
1573
1850
Summary of Contents for RRNL
Page 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 40: ...40 FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 80: ...80 FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS...
Page 81: ...81 FIGURE 36 WIRING DIAGRAM...
Page 82: ...82 FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL...
Page 83: ...83 FIGURE 38 WIRING DIAGRAM...
Page 84: ...84 FIGURE 39 WIRING DIAGRAM...
Page 85: ...85 FIGURE 40 WIRING DIAGRAM...
Page 86: ...86 FIGURE 41 WIRING DIAGRAM...
Page 87: ...87 FIGURE 42 WIRING DIAGRAM...
Page 88: ...88 FIGURE 43 WIRING DIAGRAM...
Page 91: ...91 FIGURE 46 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 93: ...93 FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 106: ...106 15 SECOND PREPURGE FIGURE 61...