59
GENERAL DATA - RRPL- MODELS
NOMINAL SIZES 2-5 TONS [7-15.8 kW]
Model RRPL- Series
B048CK08
B048CK10
B048JK06(E/X)
B048JK08(E/X)
Cooling Performance
1
Continued ->
Gross Cooling Capacity Btu [kW]
50,500 [14.8]
50,500 [14.8]
50,500 [14.8]
50,500 [14.8]
EER/SEER
2
12/14
12/14
12/14
12/14
Nominal CFM/ARI Rated CFM [L/s]
1600/1600 [755/755]
1600/1600 [755/755]
1600/1600 [755/755]
1600/1600 [755/755]
ARI Net Cooling Capacity Btu [kW]
49,000 [14.36]
49,000 [14.36]
49,000 [14.36]
49,000 [14.36]
Net Sensible Capacity Btu [kW]
34,990 [10.25]
34,990 [10.25]
34,990 [10.25]
34,990 [10.25]
Net Latent Capacity Btu [kW]
14,010 [4.1]
14,010 [4.1]
14,010 [4.1]
14,010 [4.1]
Net System Power kW
4.08
4.08
4.08
4.08
Heating Performance (Gas)
4
Heating Input Btu [kW]
80,000 [23.44]
100,000 [29.3]
60,000 [17.58]
80,000 [23.44]
Heating Output Btu [kW]
64,800 [18.99]
81,000 [23.73]
47,000 [13.77]
62,000 [18.17]
Temperature Rise Range ºF [ºC]
40-70 [22.2/38.9]
45-85 [25/47.2]
30-60 [16.7/33.3]
40-70 [22.2/38.9]
AFUE %
80
80
80
80
Steady State Efficiency (%)
81
81
81
81
No. Burners
4
5
3
4
No. Stages
1
1
1
1
Gas Connection Pipe Size in. [mm]
0.5 [12.7]
0.5 [12.7]
0.5 [12.7]
0.5 [12.7]
Compressor
No./Type
1/Scroll
1/Scroll
1/Scroll
1/Scroll
Outdoor Sound Rating (dB)
5
78
78
78
78
Outdoor Coil - Fin Type
Louvered
Louvered
Louvered
Louvered
Tube Type
Rifled
Rifled
Rifled
Rifled
Tube Size in. [mm] OD
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
16.23 [1.51]
16.23 [1.51]
16.23 [1.51]
16.23 [1.51]
Rows / FPI [FPcm]
2 / 22 [9]
2 / 22 [9]
2 / 22 [9]
2 / 22 [9]
Indoor Coil - Fin Type
Louvered
Louvered
Louvered
Louvered
Tube Type
Rifled
Rifled
Rifled
Rifled
Tube Size in. [mm]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
7.39 [0.69]
7.39 [0.69]
7.39 [0.69]
7.39 [0.69]
Rows / FPI [FPcm]
2 / 15 [6]
2 / 15 [6]
2 / 15 [6]
2 / 15 [6]
Refrigerant Control
TX Valves
TX Valves
TX Valves
TX Valves
Drain Connection No./Size in. [mm]
1/0.75 [19.05]
1/0.75 [19.05]
1/0.75 [19.05]
1/0.75 [19.05]
Outdoor Fan - Type
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter in. [mm]
1/22 [558.8]
1/22 [558.8]
1/22 [558.8]
1/22 [558.8]
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
CFM [L/s]
3300 [1557]
3300 [1557]
3300 [1557]
3300 [1557]
No. Motors/HP
1 at 1/3 HP
1 at 1/3 HP
1 at 1/3 HP
1 at 1/3 HP
Motor RPM
1075
1075
1075
1075
Indoor Fan - Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used/Diameter in. [mm]
1/10x9 [254x229]
1/10x9 [254x229]
1/10x9 [254x229]
1/10x9 [254x229]
Drive Type/No. Speeds
Direct/3
Direct/3
Direct/3
Direct/3
No. Motors
1
1
1
1
Motor HP
3/4
3/4
3/4
3/4
Motor RPM
1075
1075
1075
1075
Motor Frame Size
48
48
48
48
Filter - Type
Field Supplied
Field Supplied
Field Supplied
Field Supplied
Furnished
No
No
No
No
(NO.) Size Recommended in. [mm x mm x mm]
(1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g]
161.2 [4570]
161.2 [4570]
161.2 [4570]
161.2 [4570]
Weights
Net Weight lbs. [kg]
457 [207]
462 [210]
461 [209]
466 [211]
Ship Weight lbs. [kg]
497 [225]
502 [228]
501 [227]
506 [230]
NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Heating Performance limit ettings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. AFUE is rated in accordance with DOE test procedures.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Summary of Contents for RRNL
Page 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 40: ...40 FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 80: ...80 FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS...
Page 81: ...81 FIGURE 36 WIRING DIAGRAM...
Page 82: ...82 FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL...
Page 83: ...83 FIGURE 38 WIRING DIAGRAM...
Page 84: ...84 FIGURE 39 WIRING DIAGRAM...
Page 85: ...85 FIGURE 40 WIRING DIAGRAM...
Page 86: ...86 FIGURE 41 WIRING DIAGRAM...
Page 87: ...87 FIGURE 42 WIRING DIAGRAM...
Page 88: ...88 FIGURE 43 WIRING DIAGRAM...
Page 91: ...91 FIGURE 46 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 93: ...93 FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A...
Page 106: ...106 15 SECOND PREPURGE FIGURE 61...