- 140 -
MULTI TYPE
2, 3, 4 R
O
OMS TYPE
11.
Exit the function setting mode by pressing the RESET button.
To set custom code , , or , perform same procedures for each code.
z
Setting up each indoor unit
Repeat step from 1. to 11. to set up each indoor unit. If the custom code is other than " ", steps from
1. to 4. and 11. need to be performed.
z
Resetting the power after setting up function of all indoor units
NOTES:
• If the reset is not performed, function can not be read correctly.
• After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
– After the 2 minutes has passed, power can be restored.
– The set function is stored in the PCB and will remain in memory even when the power of
indoor unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
• Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
Once the RESET button is pressed on the remote controller, the operation mode will be set to the
AUTO MODE.
Adjust the operation mode to either cooling or heating before starting the operation of the air condi-
tioner.
NOTE:
If custom code other than " " is set, the remote control must be set accordingly to the indoor
unit setting.
RESET
Summary of Contents for RICH07AVFJ
Page 8: ......
Page 20: ...12...
Page 45: ...37...
Page 46: ...38...
Page 58: ...50 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 59: ...51 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 60: ...52...
Page 61: ...53 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 68: ...60...
Page 69: ...61 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 70: ...62 MULTI TYPE 2 3 4 ROOMS TYPE Models RIWH18AVFJ and RIWH24AVFJ...
Page 71: ...63 MULTI TYPE 2 3 4 ROOMS TYPE 5 4 Floor type Models RIFH9AVFJ RIFH12AVFJ and RIFH15AVFJ...
Page 92: ...84 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 93: ...85 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 94: ...86 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 95: ...87 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 96: ...88 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 114: ...106 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 123: ...115 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 124: ...116 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 125: ...117 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 177: ...169 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 178: ...170 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 190: ...182 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 191: ...Part 2 OUTDOOR UNIT 2 ROOMS TYPE MULTI TYPE ROMH18AFXZJ...
Page 197: ...189 OUTDOOR UNIT ROMH18AFXZJ 4 Refrigerant circuit 4 1 Model ROMH18AFXZJ...
Page 198: ...190 OUTDOOR UNIT ROMH18AFXZJ 5 Wiring diagram 5 1 Model ROMH18AFXZJ...
Page 221: ...Part 3 OUTDOOR UNIT 3 ROOMS TYPE MULTI TYPE ROMH24AFXZJ...
Page 228: ...220 OUTDOOR UNIT ROMH24AFXZJ 4 Refrigerant circuit 4 1 Model ROMH24AFXZJ...
Page 229: ...221 OUTDOOR UNIT ROMH24AFXZJ 5 Wiring diagram 5 1 Model ROMH24AFXZJ...
Page 265: ...Part 4 OUTDOOR UNIT 4 ROOMS TYPE MULTI TYPE ROMH36AFXZJ...
Page 273: ...265 OUTDOOR UNIT ROMH36AFXZJ 5 Wiring diagram 5 1 Model ROMH36AFXZJ...