- 180 -
MULTI TYPE
2, 3, 4 R
O
OMS TYPE
Condition
Contents
Countermeasures (Reference)
When inside
the ceiling is
high
temperature
and high
humidity.
When the indoor unit is installed where the inside of
the ceiling is 30°C (86°F) RH80% or greater, the dew
point temperature of the outer perimeter may
become higher than the cabinet surface temperature
and moisture will condense on the surface of the
cabinet and water drops may fall inside the room.
ĺ
Refer to Fig. A.
In addition, the humidity may vary considerably the
same as when the inside of the ceiling is close to
hermetically sealed and used as the outside air
intake path.
1. Add heat insulating material to
the outside of the indoor unit
cabinet.
*Regarding the cassette
type, use of optional High
humidity correspondence
kit is recommended.
2. Strengthen the heat insulating
material of the refrigerant
piping and drain piping too.
ĺ
Refer to Fig. B.
3. When the humidity inside the
ceiling changes considerably,
install a ventilation port.
Moist air curve
Condition which
requires addition
of outside heat
insulation
Relative humidity 80%
Dry bulb temperature 30°C (86°F)
Fig. A
Work method when reinforcing the heat insulation
of on-site piping
Fig. B
Slit of heat insulating
material facing
upward
Covered gas
pipe (heat
insulation
strengthened)
Heat insulating
material (procured at
the site)
Small exposed part
of copper pipe is
desirable.
Fit tightly
(purpose is to
cover the sealant)
Binding material
Flare connection
To indoor unit
Heat insulation
reinforcement material
(procured at the site)
Summary of Contents for RICH07AVFJ
Page 8: ......
Page 20: ...12...
Page 45: ...37...
Page 46: ...38...
Page 58: ...50 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 59: ...51 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 60: ...52...
Page 61: ...53 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 68: ...60...
Page 69: ...61 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 70: ...62 MULTI TYPE 2 3 4 ROOMS TYPE Models RIWH18AVFJ and RIWH24AVFJ...
Page 71: ...63 MULTI TYPE 2 3 4 ROOMS TYPE 5 4 Floor type Models RIFH9AVFJ RIFH12AVFJ and RIFH15AVFJ...
Page 92: ...84 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 93: ...85 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 94: ...86 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 95: ...87 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 96: ...88 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 114: ...106 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 123: ...115 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 124: ...116 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 125: ...117 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 177: ...169 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 178: ...170 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 190: ...182 MULTI TYPE 2 3 4 ROOMS TYPE...
Page 191: ...Part 2 OUTDOOR UNIT 2 ROOMS TYPE MULTI TYPE ROMH18AFXZJ...
Page 197: ...189 OUTDOOR UNIT ROMH18AFXZJ 4 Refrigerant circuit 4 1 Model ROMH18AFXZJ...
Page 198: ...190 OUTDOOR UNIT ROMH18AFXZJ 5 Wiring diagram 5 1 Model ROMH18AFXZJ...
Page 221: ...Part 3 OUTDOOR UNIT 3 ROOMS TYPE MULTI TYPE ROMH24AFXZJ...
Page 228: ...220 OUTDOOR UNIT ROMH24AFXZJ 4 Refrigerant circuit 4 1 Model ROMH24AFXZJ...
Page 229: ...221 OUTDOOR UNIT ROMH24AFXZJ 5 Wiring diagram 5 1 Model ROMH24AFXZJ...
Page 265: ...Part 4 OUTDOOR UNIT 4 ROOMS TYPE MULTI TYPE ROMH36AFXZJ...
Page 273: ...265 OUTDOOR UNIT ROMH36AFXZJ 5 Wiring diagram 5 1 Model ROMH36AFXZJ...