
4
GENERAL
The information contained in this manual has been prepared to assist in the proper
installation, operation and maintenance of the air conditioning system. Improper
installation, or installation not made in accordance with these instructions, can
result in unsatisfactory operation and/or dangerous conditions (noise and compo-
nent failure), and can cause the related warranty not to apply.
Read this manual and any instructions packaged with separate equipment required
to make up the system prior to installation. Retain this manual for future reference.
To achieve optimum efficiency and capacity, the indoor cooling coils listed in the
condensing unit specification sheet should be used.
APPLICATION
Before specifying any air conditioning equipment, a survey of the structure and a
heat gain calculation must be made. A heat gain calculation begins by measuring
all external surfaces and openings that gain heat from the surrounding air and
quantifying that heat gain. A heat gain calculation also calculates the extra heat
load caused by sunlight and by humidity removal.
Air conditioning systems are sized on the cooling load calculation. There are two
capacities that enable the equipment to provide comfort. The first is sensible capacity.
Sensible heat is the heat energy measured on the dry bulb thermometer as it is
added or removed.
The second form of heat is called latent or hidden heat. This is heat held in the
humidity in the air.
A properly-sized unit removes both forms of heat, producing a comfortable living
space. An oversized system cycles on and off too quickly and does not properly
remove humidity, producing an uncomfortable living space. Select the indoor and
outdoor equipment combination based on the manufacturer’s engineering data.
After the equipment combination has been selected, satisfying both sensible and
latent conditioning requirements, the system must be properly installed. Only then
can the unit provide the comfort the manufacturer intends.
There are several factors that the installers must consider:
•
Outdoor unit location
•
Proper equipment evacuation
•
System refrigerant charge
•
Indoor unit airflow
•
Indoor unit blower speed
•
Supply and return air duct design and sizing
•
System air balancing
•
Diffuser and return air grille location and sizing
!
WARNING
THE MANUFACTURER’S WAR-
RANTY DOES NOT COVER ANY
DAMAGE OR DEFECT TO THE
AIR CONDITIONER CAUSED BY
THE ATTACHMENT OR USE OF
ANY COMPONENTS. ACCES-
SORIES OR DEVICES (OTHER
THAN THOSE AUTHORIZED BY
THE MANUFACTURER) INTO,
ONTO OR IN CONJUNCTION
WITH THE AIR CONDITIONER.
YOU SHOULD BE AWARE THAT
THE USE OF UNAUTHORIZED
COMPONENTS, ACCESSORIES
OR DEVICES MAY ADVERSELY
AFFECT
THE
OPERATION
OF THE AIR CONDITIONER AND
MAY ALSO ENDANGER LIFE
AND PROPERTY. THE MANUFAC-
TURER
DISCLAIMS
ANY
RESPONSIBILITY FOR SUCH
LOSS OR INJURY RESULTING
FROM THE USE OF SUCH
UNAUTHORIZED COMPONENTS,
ACCESSORIES OR DEVICES.
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL/METERING DEVICE
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
TABLE 1
(-)ARL-JEZ ELECTRICAL DATA
Model
Number
RARL-
Phase
Frequency
(Hz)
Voltage
(Volts)
Compressor
Fan
Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil
Weight
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s}
Refrig.
Per
Circuit
Oz. [g]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
ELECTRICAL
PHYSICAL
Rated Load
Amperes
(RLA)
Locked
Rotor
Amperes
(LRA)
Rev. 4/11/2012 ARL-JEZ
0245JEZ
1-60-208/230
10.3/10.3
52
0.75
14/14
20/20
20/20
15.82 [1.47]
1
2285 [1078]
115 [3260]
209 [94.8]
222 [100.7]
025JEZ
1-60-208/230
11.7/11.7
58.3
0.75
16/16
20/20
25/25
15.82 [1.47]
1
2285 [1078]
104 [2948]
197 [89.4]
210 [95.3]
037JEZ
1-60-208/230
16.7/16.7
82
2.8
24/24
30/30
40/40
23.01 [2.14]
1
3400 [1604]
150 [4252]
247.5 [112.3]
260.5 [118.2]
038JEZ
1-60-208/230
15.3/15.3
83
1
21/21
25/25
35/35
23.01 [2.14]
1
3400 [1604]
186 [5273]
216 [98]
229 [103.9]
048JEZ
1-60-208/230
21.2/21.2
96
1
28/28
35/35
45/45
23.01 [2.14]
2
3400 [1604]
150 [4252]
245 [111.1]
258 [117]
049JEZ
1-60-208/230
21.2/21.2
104
1
28/28
35/35
45/45
23.01 [2.14]
1
3400 [1604]
180 [5103]
247 [112]
260 [118]
060JEZ
1-60-208/230
25.6/25.6
118
2.8
35/35
45/45
60/60
23.01 [2.14]
2
3500 [1652]
220 [6237]
314 [142.4]
327 [148.3]
061JEZ
1-60-208/230
28.8/28.8
152.9
2.8
39/39
50/50
60/60
23.01 [2.14]
2
3500 [1652]
243 [6889]
283 [128.4]
296 [134.3]
Rev. 4/20/2012 (-)ASL-JEZ ELECTRONICS DATA
024JEZ
1-60-208/230
10.3/10.3
52
0.5
14/14
20/20
20/20
15.8 [1.47]
1
2500 [1180]
144 [4082]
250.5 [107]
263.5 [107]
036JEZ
1-60-208/230
16.7/16.7
82
2.8
24/24
30/30
40/40
23.01 [2.14]
1
3400 [1604]
150 [4252]
247.5 [112.3]
260.5 [118.2]
ELECTRICAL & PHYSICAL DATA
Summary of Contents for ARL-JEZ 16 Seer Series
Page 36: ...36 FIGURE 5 ARL 025 038 049 WIRING DIAGRAM ...
Page 37: ...37 FIGURE 6 ARL 061 JEZ ASL 024 JEC ASL 025 JEZ ASL 036 JEC ASL 037JEZ WIRING DIAGRAM ...
Page 38: ...38 ...
Page 39: ...39 ...
Page 40: ...40 CM 0213 ...