
34
SYSTEM CHARGE TROUBLESHOOTING
SUPERHEAT CALCULATION
1. Measure the suction pressure at the suction line service valve.
2. Convert the suction pressure to saturated temperature. See Table 9.
3. Measure the temperature of the suction line at the suction line service valve.
4. Compare the temperature of the suction line to the saturated temperature.
5. The difference between saturated temperature and suction line temperature is
the superheat. Superheat normal range 9° to 16°.
SUBCOOLING CALCULATION
1. Measure the liquid pressure at the liquid line service valve.
2. Convert the liquid line pressure to saturated temperature. See Table 9.
3. Measure the liquid line temperature at the liquid line service valve.
4. Compare the liquid line temperature to the saturated temperature.
5. The difference between saturated temperature and liquid line temperature is the
subcooling. Subcooling normal range 5° to 14°.
LOW VOLTAGE SOLENOID TROUBLESHOOTING
Recommended troubleshooting process
1. Begin diagnosis at the ICC:
Check for flashing codes at the ICC.
2. Check compressor amperage:
Operate the system and measure compressor amperage. Cycle the solenoid on
and off at ten plus second intervals by applying and removing the molded plug
(make certain the ICC is in 2nd stage; large C on the 7-segment LED). Wait five
seconds after power is applied via the molded plug before taking a reading. The
compressor amperage should go up or down at least 25 percent (a saturated
condensing temperature below 80°F may not produce as wide a change in
amperage).
3. Check the voltage supplied to the solenoid:
Remove the solenoid plug from the compressor. With the unit running and the
thermostat calling for Y2 (24VAC at the yellow/blue wire; large C on the 7-seg-
ment LED), test the voltage output at the plug with a DC voltmeter. The reading
should be 4 to 18 volts. If not, unplug the harness from the ICC harness and
check voltage at the pins of the ICC harness. The ICC will not power the sole-
noid if the compressor is not running or fault code 1 or 9 is active.
4. Check solenoid resistance:
Measure the solenoid resistance at the pins on the compressor. The resistance
should be 32 to 60 ohms depending on compressor temperature. If the coil resis-
tance is infinity, much lower than 32 ohms, or is grounded the compressor must
be replaced.
TABLE 10
AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPS
AIR CONDITIONING SYSTEM
TROUBLESHOOTING TIPS
TABLE 9
TEMPERATURE PRESSURE CHART
TEMP
R-410A
(Deg. F)
PSIG
-150
—
-140
—
-130
—
-120
—
-110
—
-100
—
-90
—
-80
—
-70
—
-60
0.4
-50
5.1
-40
10.9
-35
14.2
-30
17.9
-25
22.0
-20
26.4
-15
31.3
-10
36.5
-5
42.2
0
48.4
5
55.1
10
62.4
15
70.2
20
78.5
25
87.5
30
97.2
35
107.5
40
118.5
45
130.2
50
142.7
55
156.0
60
170.1
65
185.1
70
201.0
75
217.8
80
235.6
85
254.5
90
274.3
95
295.3
100
317.4
105
340.6
110
365.1
115
390.9
120
418.0
125
446.5
130
476.5
135
508.0
140
541.2
145
576.0
150
612.8
DISCHARGE
SUCTION
SUPERHEAT SUBCOOLING
COMPRESSOR
PRESSURE
PRESSURE
AMPS
Overcharge
High
High
Low
High
High
Undercharge
Low
Low
High
Low
Low
Liquid Restriction (Drier)
Low
Low
High
High
Low
Low Evaporator Airflow
Low
Low
Low
Low
Low
Dirty Condenser
High
High
Low
Low
High
Low Outside Ambient Temperature
Low
Low
High
High
Low
Inefficient Compressor
Low
High
High
High
Low
TXV Sensing Bulb Charge Lost
Low
Low
High
High
Low
Poorly Insulated Sensing Bulb
High
High
Low
Low
High
SYSTEM PROBLEM
INDICATORS
Summary of Contents for ARL-JEZ 16 Seer Series
Page 36: ...36 FIGURE 5 ARL 025 038 049 WIRING DIAGRAM ...
Page 37: ...37 FIGURE 6 ARL 061 JEZ ASL 024 JEC ASL 025 JEZ ASL 036 JEC ASL 037JEZ WIRING DIAGRAM ...
Page 38: ...38 ...
Page 39: ...39 ...
Page 40: ...40 CM 0213 ...