24
7 -Segment
Display
Code
Diagnostic Description
Status / Possible Cause -Troubleshooting
Information
0
Standby
Standby - No call for operation
c
Y1
First Stage or Single Stage Unit Operation
L
4
Status and Diagnostic Description
C
Y2
Second stage unit operation
(2-stage unit only)
c or
C Flashing
Anti-Short Cycle Timer (3 minutes) or
Minimum Run Timer (30 seconds)
Waiting for anti-short cycle timer to expire
Waiting for minimum run timer to expire
F
1. Low voltage wiring damage or miswired
1 (*)
Compressor Running Extremely Long Run
Cycle (Cooling mode only)
1. Low refrigerant charge
2. Air ducts have substantial leakage
3. Check thermostat operation
4. Dirty filter
5. Dirty outdoor coil
2 (*)
Pressure Control Trip (L terminal output only)
1. (See faults 21, L21, 23, L23)
21 (***)
Low Pressure Control Trip
Note: Low-pressure control is ignored for 90
seconds after call for unit operation.
restart the unit after the pressure control
automatically re-closes.
Unit will try to restart 3 times in the same
thermostat call for operation (Y1) before
lockout (fault L21).
1. Unit is low on refrigerant charge
2. Indoor coil is frozen (cooling mode)
3. Dirty indoor coil or filter (cooling mode)
4. Indoor blower is not running (cooling mode)
5. TEV is not operating correctly
L21 (**)
Lockout - Low Pressure Control Trip (**)
LPC tripped three consecutive times in same
thermostat call
23 (***)
High Pressure Control Trip
restart the unit after the pressure control
automatically re-closes.
Unit will try to restart 3 times in the same
thermostat call for operation (Y1) before
lockout (fault L23)
1. Outdoor coil is dirty (cooling mode)
2. Outdoor fan is not running (cooling mode)
3. Dirty indoor coil or filter (heat pump mode)
4. Liquid line restriction (filter drier blocked, etc.)
5. Excessive refrigerant charge
L23 (**)
Lockout - High Pressure Control Trip (**)
HPC tripped three consecutive times in same
thermostat call
25
Outdoor Ambient Temperature Sensor
27
Abnormal Low Line or No Line Voltage
(See unit nameplate for operating voltage)
1. Check incoming line voltage to the disconnect
and unit
2. Check wiring connections
28
Abnormal High Line Voltage
1. Check line voltage
3 (*)
Short Cycling
1. Check thermostat for intermittent demand
signal
2. Check thermostat location in zone (too close to
discharge grill)
Active Protection
– The ICC will try to
Active Protection
– The ICC will try to
1. ICC board sensor damaged (ICC
will continue to operate)
ICC Board Fuse Open
Summary of Contents for ARL-JEZ 16 Seer Series