SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
Short cycling of compressor (cont.)
Low charge
Check system charge
Low evaporator air flow
Dirty coil
Dirty filter
Duct too small or restricted
Faulty run capacitor
Replace
Faulty internal overload
Replace compressor
ELECTRICAL
(See Control Diagnostics)
SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
No voltage on line side
Blown fuses or tripped circuit breaker
Check for short in wiring or unit
of control board
Improper wiring
Re-check wiring diagram
Improper voltage
High voltage
Wrong unit
Power supply problem
Low voltage
Wrong unit
Power supply problem
Wiring undersized
Loose connections
CONTAMINATION
SYMPTOMS
POSSIBLE CAUSE
CHECK OR REMEDIES
Moisture
Poor evacuation on installation
In each case, the cure is the same.
or during service
Recover refrigerant. Add filter drier,
evacuate and re-charge
High head pressure
Non-condensibles air
Unusual head and suction readings
Wrong refrigerant
Foreign Matter-
copper filings
Copper tubing cuttings
Copper oxide
Dirty copper piping
Welding scale
Nitrogen not used
Soldering flux
Adding flux before seating
copper part way
Excess soft solder
Wrong solder material
CONTINUED