
35
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
• Power off or loose electrical connection
• Check for correct voltage at contactor in condensing unit
• Thermostat out of calibration-set too high
• Reset
• Defective contactor
• Check for 24 volts at contactor coil - replace if contacts are
open
• Blown fuses / tripped breaker
• Replace fuses / reset breaker
• Transformer defective
• Check wiring-replace transformer
• High pressure control open (if provided)
• Reset-also see high head pressure remedy-The high pressure
control opens at 450 PSIG
Outdoor fan runs, compressor
• Run or start capacitor defective
• Replace
doesn’t
• Start relay defective
• Replace
• Loose connection
• Check for correct voltage at compressor -
check & tighten all connections
• Compressor stuck, grounded or open motor winding,
• Wait at least 2 hours for overload to reset.
open internal overload.
If still open, replace the compressor.
• Low voltage condition
• Add start kit components
Insufficient cooling
• Improperly sized unit
• Recalculate load
• Improper indoor airflow
• Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge
• Charge per procedure attached to unit service panel
• Air, non-condensibles or moisture in system
• Recover refrigerant, evacuate & recharge, add filter drier
Compressor short cycles
• Incorrect voltage
• At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector
• Replace - check for correct voltage
• Refrigerant undercharge
• Add refrigerant
Registers sweat
• Low indoor airflow
• Increase speed of blower or reduce restriction - replace air
filter
High head-low vapor pressures
• Restriction in liquid line, expansion device or filter drier
• Remove or replace defective component
• Flowcheck piston size too small
• Change to correct size piston
• Incorrect capillary tubes
• Change coil assembly
High head-high or normal vapor
• Dirty outdoor coil
• Clean coil
pressure - Cooling mode
• Refrigerant overcharge
• Correct system charge
• Outdoor fan not running
• Repair or replace
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
Low head-high vapor pressures
• Flowcheck piston size too large
• Change to correct size piston
• Defective Compressor valves
• Replace compressor
• Incorrect capillary tubes
• Replace coil assembly
Low vapor - cool compressor -
• Low indoor airflow
• Increase speed of blower or reduce restriction - replace air
iced indoor coil
filter
• Operating below 65°F outdoors
• Add Low Ambient Kit
• Moisture in system
• Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure
• Excessive load
• Recheck load calculation
• Defective compressor
• Replace
Fluctuating head & vapor
• TXV hunting
• Check TXV bulb clamp - check air distribution on coil - replace
pressures
TXV
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
Gurgle or pulsing noise at
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
expansion device or liquid line
Compressor runs, ECM
• 24VAC signal not present at yellow fan wire
• Check for correct thermostat connections
outdoor fan doesn't
• Common signal not present at blue fan wire
• Verify blue fan wire is connected to the common side
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
WARNING
!
How do I know if the low voltage solenoid is switching?
Go through the four standard troubleshooting steps. If inconclusive do the following:
1. Make sure the compressor is OFF.
2. Apply 18 to 28V AC to the solenoid pins at the pump.
3. The solenoid should make an audible click as it is energized.
4. Remove the AC signal to the solenoid pins.
5. The solenoid should make an audible click as it de-energizes.
IMPORTANT: Do not operate the compressor with 24VAC applied to the low volt-
age solenoid pins. Applying 24VAC to the solenoid pins can overheat it over time
and cause solenoid failure.
Use the above steps for troubleshooting only!
TROUBLE SHOOTING CHART
Summary of Contents for ARL-JEZ 16 Seer Series
Page 36: ...36 FIGURE 5 ARL 025 038 049 WIRING DIAGRAM ...
Page 37: ...37 FIGURE 6 ARL 061 JEZ ASL 024 JEC ASL 025 JEZ ASL 036 JEC ASL 037JEZ WIRING DIAGRAM ...
Page 38: ...38 ...
Page 39: ...39 ...
Page 40: ...40 CM 0213 ...