TM049 27L Continuous Flow Service Instructions
REV AL
– Issued April 2019
This document is stored and maintained electronically by Rheem Technical Support.
All printed copies are deemed “uncontrolled”.
36
Hot water tap closed
Operational Flow Chart 3
G.I.S.V (SVO) off
or
[S.V. 1-3 (SV1-3) off]
YES
YES
NO
YES
Approx. 6 minutes later
P.G.F.R Valve at
minimum
4
5
Post Purge Shut Down Function
Water flow sensor off
Fan motor at minimum
I.U.I off
S.V. 1-3 (SV1-3)
failure
80 Flashing
8 seconds later
NO
G.I.S.V (SV0) failure
51 Flashing
G.I.S.V (SVO) off
[S.V. 1-3 (SV1-3) off]
P.G.F.R Valve off
Fan off
YES
Abnormal combustion
NO
99 Flashing
Fan off
Isolate power
Locate and repair fault.
Clear error code 99.
S.V. 1 (SV1) off
S.V. 2 (SV2) off
Fan off
S.V. 3 (SV3) off
G.I.S.V (SV0) off
Isolate power
Locate and repair fault
and restore power
10 seconds later
10 seconds later
Flame current
detected less than
0.1uA?
Fan motor speed
checked during
operation?
Fan motor current
check ok?
P.G.F.R valve off