TM049 27L Continuous Flow Service Instructions
REV AL
– Issued April 2019
This document is stored and maintained electronically by Rheem Technical Support.
All printed copies are deemed “uncontrolled”.
56
Error Code 52
Proportional Gas Flow Regulator (PGFR) Valve fault.
Error Code 52
Check wiring, if intact replace the
control PCB.
NO
Is there voltage at the
proportional gas valve?
TEST 10
Replace the gas valve assembly.
YES
Is multi-pin plug fully inserted
into terminal P on control
PCB?
YES
Ensure multi-pin plug is fully
inserted.
NO
Error Code 61
Combustion fan failure.
Error Code 61
Is fan speed correct?
TEST 25
Replace the transformer
Replace the control PCB.
The error was likely to be
caused by a fluctuation in the
power supply. Isolate power to
clear error code.
YES
“Live” testing to be conducted. Personal Protective Clothing (PPE)
shall be worn and an RCD shall be installed between the power point
and 3-pin cord of the water heater to reduce the risk of electric shock.
Is fan motor power
supply correct?
TESTS 18 & 19
YES
NO
Is fan coil resistance
correct?
TEST 23 & 24
YES
Check wiring, if intact replace
the fan assembly.
NO
Is fan/PCB resistance
correct?
TEST 20 & 21
NO
Is transformer resistance
correct?
TEST 22
YES
NO
Replace the Power Supply
PCB
YES
Replace the fan assembly
NO