⚠ CAUTION ⚠
•
Uninsulated metal roof decks:
infrared heaters should not be installed in buildings with uninsulated
metal roof decks. Uninsulated metal roof decks will cause condensation of water vapor (contained
in the unvented heater flue gas) on the inside of the building. Metal roof decks must be insulated
using built-up insulation and roofing on the exterior or inside insulation that is not permeable
to water vapor. Interior insulation that is permeable to water vapor must be completely sealed
with a vapor barrier.
•
High elevation:
heaters are manufactured for use at the specific elevation range stated on the
heater rating plate. Do not install a heater that is not rated for the correct elevation.
NOTES:
• For indoor installation only. Not for use in residential dwellings.
•
Installation à l’entérieur seulement. Ne pas installer dans un logement.
• A residential dwelling is a domicile intended for use by one or more persons and that includes
one or more areas, such as those used for cooking, eating, living, sleeping, or a sanitary facility.
A residential dwelling does not include an attached and detached garage, workshop, or outdoors.
Warranty
Restrictions:
•
Use for process heating applications VOIDS the warranty and CSA design certification .
•
These heaters are RESTRICTED from use for the following applications, which will also VOID the warranty and
CSA design certification .
The warranty is void if unit is:
•
Used in atmospheres containing flammable vapors or atmospheres containing chlorinated or halogenated
hydrocarbons or atmospheres containing explosive dusts .
•
Installed without proper clearance to combustible materials or in a location where the heater controls can be
subjected to ambient temperatures above 150°F (66°C) or below
−
40°F (
−
40°C) .
•
Installed at angles not approved for the model .
•
Installed for other than space heating applications .
•
Installed for residential use . THE HEATER IS NOT FOR RESIDENTIAL USE .
•
Installed outdoors .
•
Installed in enclosed swimming pool areas .
•
Altered . Units are completely factory assembled and tested .