Table 4. Required Clearances
Description
Dimension
Description
A
Side of heater
E
Mounting angle (5- to 30-degree range)
B
Back of heater
H
Stacking height (H = M
−
D)
C
Top of heater
M
Mounting height (refer to
D
Below heater
Gas
Type
Model
Unit
Size
Dimension
A
B
C
D
Required Clearance (Inches (mm))
Natural gas
RIHN
030
*
30 (762)
60 (1524)
†
80 (2032)
‡
48 (1219)
††
34 (864)
†††
110 (2794)
‡‡
060
**
30 (762)
60 (1524)
†
80 (2032)
‡
48 (1219)
††
34 (864)
†††
110 (2794)
‡‡
RIHVN
100
36 (914)
30 (762)
62 (1575)
†
105 (2667)
‡
50 (1270)
††
38 (965)
†††
135 (3429)
‡‡
150
46 (1168)
33 (838)
64 (1626)
†
125 (3175)
‡
58 (1473)
††
165 (4191)
‡‡
160
48 (1219)
33 (838)
68 (1727)
†, ††
140 (3556)
‡
180 (4572)
‡‡
200
48 (1219)
33 (838)
68 (1727)
†, ††
140 (3556)
‡
180 (4572)
‡‡
Propane
RIHL
050
30 (762)
60 (1524)
†
80 (2032)
‡
48 (1219)
††
34 (864)
†††
110 (2794)
‡‡
RIHVL
090
36 (914)
30 (762)
62 (1575)
†
105 (2667)
‡
50 (1270)
††
38 (965)
†††
135 (3429)
‡‡
120
46 (1168)
33 (838)
64 (1635)
†
125 (3175)
‡
58 (1473)
††
165 (4191)
‡‡
*
Unit size 030 of model RIHN is not available in Canada .
**
In Canada, unit size 060 of model RIHN requires the addition of a wire grid (option DN2) .
†
Units with no heat deflector mounted at a 5- to 29-degree angle .
††
Units with no heat deflector mounted at a 30-degree angle .
†††
Units with a heat deflector (option DO2) mounted at a 5- to 30-degree angle .
‡
Units with a standard reflector .
‡‡
Units with a parabolic reflector (option DM2) .
Figure 2. Clearances to Combustibles (Refer to
B
A
A
C
D
B
D
C
E
E
B
D
C
3D VIEW
ALL UNIT SIZES
STACKING HEIGHT
D
H
M
UNIT SIZES 030, 050, 060
GENERAL INFORMATION—CONTINUED
Clearances—Continued