Page No 6 Reznor, Guardian 1 Phase Electric Heat with Signal Pro, Installation Manual, EN 2021-11, D301375 Iss 0
TD
Technical data
Data
Fan speed Unit 1000E-1PH 1500E-1PH 2000E-1PH
All models
Maximum door width
L, M, H
m
1.0
1.5
2.0
Maximum mounting height standard capacity
L, M
m
3.0
Maximum mounting height high capacity
H
m
4.0
Maximum air volume
L
m
3/
h
1150
1730
2300
M
m
3
/h
1440
2270
2880
H
m
3
/h
1800
2700
3600
Maximum velocity at 0 metre
L
m/s
6.4
M
m/s
8
8.4
8
H
m/s
10
10.1
10
Maximum velocity at 1 metre
H
m/s
5.6
5.2
5.4
Maximum velocity at 2 metre
H
m/s
3.8
3.5
3.7
Maximum velocity at 3 metre
H
m/s
2.8
2.5
2.8
Motor power
L, M, H
W
365
530
730
Noise level @ 3m free field
L
dB(A)
52
M
dB(A)
55
H
dB(A)
59
Program panel control wiring
RJ45 (pre-wired cable required)
Low voltage cable terminal size
1.5mm
2
MAX
Electric Heat
Electrical supply
L, M, H
230V 1 phase 50Hz
Heating capacity
L, H
kW
6
6
8
Total electrical load (Maximum)
A
28.9
28.9
37.6
Max temperature rise
L
°C
14
9
9
M
°C
11
7
7
H
°C
9
6
6
Weight
kg
34.5
52
64.5
External fuse size (D type MCB)
H
A
32
32
40
Table 1 Technical data
Fuse
Guardian air curtain control is fitted with a T1H (1A) 5mm x 20mm control circuit fuse.
Summary of Contents for GUARDIAN GB 1000
Page 2: ......