Page No 12 Reznor, Guardian 1 Phase Electric Heat with Signal Pro, Installation Manual,  EN 2021-11, D301375 Iss 0

I

Installation 

Mounting

Guardian GS,GR and GB air curtain units are 
designed to be installed horizontally directly 
over the door opening on the inside of the 
building, against a wall or ceiling. 

Care must be taken to allow 
complete free air movement into 
the inlet grilles of the unit to  

               ensure the correct working       
               operation of the air curtain. The  
               honeycomb outlet should be as  
               close to the top of the door as  
               possible and can be angled       
               towards the door from 0° to -5°.  
               Ensure to cover the entire door  
               width. See figure 8

Units can be mounted adjacent to each other 
to cover the full door opening across wider 
entrances.

The GS units are designed for 
surface mounting and should not 
be placed into a ceiling void, due  

               to possible obstruction of airflow  
               and difficulty in routine cleaning  
               and maintenance. Use the GR for  
               these types of applications

It is the sole responsibility of the 
installer to ensure that the points 
of attachment to the building are  

               sound.

Verification with the consultant/
architect or owner of the 
building is recommended to      

               ensure that a sound, stable    
               installation can be achieved.

Figure 8 Honeycomb outlet position near 
to the door adjustable angle of 0 to -5°

Electrical supply.

Units require a connection to 1 phase 230V 
power supply only.

1000 and 1500 models consume 6kW and 
2000 models consume 8kW.

The appliance must be connected to the 
supply via an appropriate a switched fused 
isolator, having a contact separation of greater 
than 3mm. See technical data for fuse rating 
on page 6

Once the covers have been removed, the 
installation engineers terminal block is located 
to the right hand side of the unit. This terminal 
block is used for the connection of the mains 
supply and additional controls, for example 
door switch. Wire in accordance to the 
diagram in the wiring section, on page 17 

For safety reasons, a sound earth 
connection must always be made 
to the unit before it is put in to  

               use. The unit should be wired in  
 

    accordance with IEE Regulations  

 

    for the Electrical Equipment of  

 

    Buildings.

The display panel is connected to 
the control panel (base unit) via a 
pre-wired RJ45 cable maximum 
length of 100m. (10m supplied as  

 

     standard). It is recommended that  

 

     this cable is run separately within its  

 

     own trunking to avoid external  

                 interference.

Summary of Contents for GUARDIAN GB 1000

Page 1: ...s document carefully before commencing installation commissioning and or servicing Leave it with the end user site agent to be placed in their premises technical file after installation WARNING Improp...

Page 2: ......

Page 3: ...auto mode 20 4 All on mode 20 5 All heat off 20 6 Set door open temperature 20 7 Set heat on off 21 8 Set overtime 21 9 Set time and days 21 10 Set time program 21 11 Menu end 21 Engineers instruction...

Page 4: ...vailable at an additional cost The display program panel allows the user to control either a single air curtain or a network of up to 16 air curtains Easy programming the end users simply select wheth...

Page 5: ...Important notice to installers Before installation check the local distribution conditions supply voltage are compatible Installation assembly commissioning service and maintenance procedures must be...

Page 6: ...velocity at 1 metre H m s 5 6 5 2 5 4 Maximum velocity at 2 metre H m s 3 8 3 5 3 7 Maximum velocity at 3 metre H m s 2 8 2 5 2 8 Motor power L M H W 365 530 730 Noise level 3m free field L dB A 52 M...

Page 7: ...ntry and prevents combustible surfaces overheating The minimum mounting height floor to grille outlet is 1 8m The recommended maximum mounting height is 3m for standard fan setting 4m for high Dimensi...

Page 8: ...ces It is recommended that a minimum clearance of 100mm is allowed around the case The clearance allows for cable entry and prevents combustible surfaces overheating The minimum mounting height floor...

Page 9: ...4 112 114 3 830 1360 1884 4 226 5 1060 1584 2111 6 448 7 1125 1650 2177 8 436 9 300 10 427 487 Figure 4 3 GB Side view Table 4 GB Dimensions Clearance distances It is recommended that a minimum cleara...

Page 10: ...display panel is supplied with an industry standard plastic double surface mounted socket box Alternatively the display panel can be flush mounted using a customer supplied plastic or metal flush con...

Page 11: ...al EN 2021 11 D301375 Iss 0 Page No 11 TD Component layout Figure 6 Component layout GS Location Component 1 Control panel 2 Installer terminal block 3 Fan 4 Fan motor 5 Fan deck 6 Resistor 1500 only...

Page 12: ...the consultant architect or owner of the building is recommended to ensure that a sound stable installation can be achieved Figure 8 Honeycomb outlet position near to the door adjustable angle of 0 to...

Page 13: ...of the lower grove in the case 3 The first cover can then be pushed to the right to release it from the screw slot see figure 10 then pull forward and lift upwards to be removed For additional covers...

Page 14: ...ins level 6 Holes are provided in the casing for cable entry Choose the appropriate hole to suit the installation Note the terminal connection block is located to the right of the unit 7 Install the c...

Page 15: ...nstructions grill Figure 16 Mounting bracket option Figure 16 1 Mounting bracket fitted to GB Signal Pro display panel The display panel can be installed using the standard double surface box supplied...

Page 16: ...e units to each terminal pair EXT Only air curtain s wired this way will respond to the sensor setting If the optional external temperature sensor is connected to the air curtain If the external tempe...

Page 17: ...itching thyristors for the heater An external circuit breaker with the appropriate rating should be installed for the protection of the installation Terminal Description Cable 3 4 Optional external sw...

Page 18: ...red RJ45 cable to the socket in the first air curtain housing See figure 25 on page 19 Connect a second RJ45 cable in to the spare RJ45 socket of the first air curtain and then take across to one of t...

Page 19: ...C Operation In normal operation the home screen displays the status of the display panel and each connected air curtain in sequence Each screen is displayed for two seconds Display Status Top line sho...

Page 20: ...o heat and no fan and then returns to default display 3 All Auto mode A single press of OK quickly starts Auto timed operation for all air curtains and then returns to default display When in Auto mod...

Page 21: ...lashing Use PLUS and MINUS to adjust hours 00 to 23 then OK Minutes starts flashing Use PLUS and MINUS to adjust minutes 00 to 59 then OK After this OK the new Time and Day is stored If MENU is presse...

Page 22: ...ss was individual then next address is flashing Use PLUS and MINUS to set address OK to modify the fab speed or MENU to exit back to engineers menu 3 Set door closed temperature Door closed temperatur...

Page 23: ...of the air curtains discovered then OK If lead air curtain address is set to OFF then the sequence finishes and returns to the engineers menu interlocks will not be enabled If lead air curtain addres...

Page 24: ...work scanned for connected air curtains and when finished returns to engineers menu If scan NO then the sequence returns to the engineers menu Note This will cause the detected network type to be rese...

Page 25: ...the air curtain on this address is not responding to the panel Display for active air curtains Electric system Where AC is address of AC with diagnostics being displayed H 1 heat on 0 heat off from AC...

Page 26: ...e the outside limit the fan will continue to run but the heat output will be off When the outside temperature is below 0 C the air outlet temperature will be the set temperature plus the elevate at ze...

Page 27: ...gs Bitswitch3 ON Modbus Address Switch Setting Modbus Address Switch Setting 16 0 24 8 17 1 25 9 18 2 26 A 19 3 27 B 20 4 28 C 21 5 29 D 22 6 30 E 23 7 31 F Modbus function codes supported Codes Descr...

Page 28: ...xt_exists Read only Set if external thermistor not fitted 13 Set_fan1 Read write Switch fan 1 14 Set_fan 2 Read write Switch fan 2 15 Set_fan 2 Read write Switch fan 2 16 Heat Read write Switch heat d...

Page 29: ...lifted out of the dog bone slot This panel can then be lifted out of the tabs at the bottom to fully release see figure 9 on page 13 2 GR units loosen the screws securing the inlet grille and hinge do...

Page 30: ...elease the carrier from the stud side on the 2m models the centre support can be moved to one side to allow the stud side to be released On the GS units peal back the tabs which retain the honeycomb o...

Page 31: ...to identify the nature of the fault however we do not recommend re setting without a thorough investigation into why the cut out operated Figure 31 Thermal cut out Display panel Any fault will be des...

Page 32: ...heat Air sensor cable disconnected Air sensor broken Check cable Replace air sensor Air sensor temp too high Fan operating no heat High ambient air temperature Incorrect motor or fan deck rotation Mot...

Page 33: ...of the unit Component 1000 1500 2000 Generic components Fan deck assembly 1026174 1026175 1026174 x 2 Signal Pro display panel 108221 RJ45 2 Resistor n a 1037491 n a Honeycomb core 1026068 1026078 102...

Page 34: ...verse the steps remembering to reconnect the temperature sensor wire which goes through the hole in the PCB Reverse the steps to install the new control panel Set the dip switch for the location and f...

Page 35: ...o 35 G 3 Remove the wires to the thermal cut out sensor two sensors on the 2 metre units and remove the thermal cut out 4 Remove the four securing nuts shake proof washer and flat washer that secure t...

Page 36: ...k com www reznor eu Nortek Global HVAC is a registered trademark of the Nortek Global HVAC lLmited Because of the continuous product innovation Nortek Global HVAC reserves the right to change product...

Reviews: