7-22
Connections and Interfaces
IndraControl L40
DOK-CONTRL-IC*L40*****-PR03-EN-P
Pin
Meaning
1
V -
2
CAN_L
3
Shield
4
CAN_H
5
V +
Fig. 7-32:
Pin assignment of the X7D connector
Note:
Cable fixing during installation required!
For further descriptions please refer to the particular system-
specific manual.
The meaning of the indicator elements (two LEDs) are listed in the
following table:
LED
Color
Status
Flash frequency
Description
Flashing
Slowly, 1 Hz
Device is in boot load mode and is waiting for a firmware
download
Flashing
Fast, 5 Hz
Firmware is loaded
Red
Acyclically
flashing
3 times fast with 5 Hz
8 times slow
0,5 Hz to 1 Hz
Hardware error detected, the device has to be exchanged,
please contact Bosch Rexroth.
Cyclically
flashing
Fast, 5 Hz
No configuration error, device is online and ready for the field
bus communication; attempt to establish a connection, but
field bus device not yet found.
Acyclically
flashing
3 times fast with 5 Hz
8 times slow
0,5 Hz to 1 Hz
During switching on: Configuration is missing, device has to
be configured
In operation: critical firmware, like e. g. timeout
Green
Statically at
-
Device has established at least one configured connection.
Stat.
Off
-
-
Device has no power supply.
Statically at
-
Device is online, connections established.
Device is connected with another master.
Device has established a connection to a slave.
Green
Flashing
Slowly, 1 Hz
Device is online, no connection established.
Configuration is missing.
Device has terminated the address verification, but no
connection to another device established.
Red
Device has no access on the bus, because of bus error.
Double addressing determined.
MNS
Off
-
-
Device is not online, the address verification is not
terminated.
Device has no supply voltage.
Fig. 7-33:
Meaning of the light emitting diodes at the DeviceNet master function
module
X7D
DeviceNet Interface
Indicator Elements