Technical data
32 Operating instructions RLD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
3.3.2
Power feedback unit REVCON RLD D0
REVCON type
RLD D0
230V
RLD D0
400V
RLD D0
460V
RLD D0
500V
RLD D0
690V
Nominal range of the
interlinked mains
voltage
U
N
[V]
220
≤
U
N
≤
240
380
≤
U
N
≤
415
440
≤
U
N
≤
480
500
600
≤
U
N
≤
700
Tolerance of the
interlinked mains
voltage
U
N
[V]
-15% /
+10%
-15% /
+10%
-15% /
+10%
-15% /
+10%
-15% /
+10%
Mains frequency
f
N
[Hz]
40 - 60
±
10 %
Overload capability
ca. 1,2 x Irms (dynamic)
Efficiency
η
[%]
Ca. 98 %
Power factor
cos
ϕ
∼
1
Fundamental
frequency component
g
∼
0,7- 0,95
*
1
Airflow requirement
m³ / h
a)
RLD D0 6-230, 10-230, 16-230, 21-230
RLD D0 28-230
RLD D0 8-400, 11-400, 18-400, 28-400, 38-400
RLD D0 50-400
RLD D0 15-460, 24-460, 33-460
RLD D0 17-500. 27-500, 37-500, 45-500
RLD D0 24-690, 45-690, :
200
b)
RLD D0 40-230, 58-230, 78-230
RLD D0 70-400, 100-400, 135-400
RLD D0 42-460, 64-460, 83-460, 105-460,
RLD D0 138-460
RLD D0 70-500, 90-500, 90-500, 115-500 :
350
c)
RLD D0 75-230*
2
RLD D0 135-400*
2
RLD D0 125-460*
2
RLD D0 70-690, 70-690, 100-690 :
450
d)
RLD D0 92-230, 116-230, 145-230
RLD D0 160-400, 200-400, 250-400
RLD D0 160-460, 230-460, 280-460
RLD D0 150-500, 250-500, 320-500
RLD D0 150-690, 200-690, 250-690
:
700
e)
RLD D0 375-460, 350-690
:
800
Power derating
[%/K]
[%/m]
40°C < Ta < 55°C
⇒
3%/K
1000m a.m.s.l.< h
≤
4000m a.m.s.l.
⇒
5%/1000m
Table 3.3.2.1
*
1
Depending on the size of the unit (nominal power and nominal voltage)
*
2
Alternative case-type with minor changed dimensions