                                                                                                                         Technical data 

 

Operating instructions RLD                                                                                            47 

ELTROPLAN

 - 

REVCON

 

       

Elektrotechnische Anlagen GmbH

 

 

REVCON

®

 - type 

RLD B0 

Max. fuse  AC 

Connection terminal  

and max. Cross section  

of the supply line* 

   24-690-50-230-A 

Siba 5012406.50    50A    690V 14x51mm 

ES 

  25mm² 

   45-690-50-230-A 

Siba 5014006.80    80A    690V 22x58mm 

ES 

  25mm² 

   70-690-50-230-A 

Siba 2018920.160 160A   690V NH 00 

ES 

  25mm² 

   90-690-50-230-A 

Siba 2018920.160 160A   690V NH 00 

ES 

  25mm² 

 150-690-50-230-A 

Siba 2018920.250 250A   690V NH 00 

ES 

150mm² 

 200-690-50-230-A 

Siba 2018920.315 315A   690V NH 00 

ES 

150mm² 

 250-690-50-230-A 

Siba 2071332.400 400A 1100V NH 01 

ES 

150mm² 

 300-690-50-230-A 

Siba 2071332.500 500A 1100V NH 01 

CL 

240mm² 

 350-690-50-230-A 

Siba 2071332.630 630A 1100V NH 01 

CL 

240mm² 

Table 3.6.1.5 

ES 

 End sleeve for strands 

CL 

 Cable lug 

*     At the fuse holder respective disconnector 

 

Series fuses REVCON RLD D0 

REVCON

®

 - type 

RLD D0 

Max. fuse  AC 

Connection terminal  

and max. Cross section  

of the supply line* 

     6-230-50-0-A 

Siba 5012406.32     32A   690V 14x51mm 

ES 

  25mm² 

   10-230-50-0-A 

Siba 5012406.40     40A   690V 14x51mm 

ES 

  25mm² 

   16-230-50-0-A 

Siba 5014006.80     80A   690V 22x58mm 

ES 

  25mm² 

   21-230-50-0-A 

Siba 5014006.100 100A   690V 22x58mm 

ES 

  25mm² 

   28-230-50-0-A 

Siba 2018920.160 160A   690V NH 00 

ES 

  25mm² 

   40-230-50-230-A 

Siba 2018920.160 200A   690V NH 00 

ES 

  50mm² 

   58-230-50-230-A 

Siba 2018920.315 315A   690V NH 00

 

ES 

  95mm² 

   78-230-50-230-A 

Siba 2018920.350 350A   690V NH 00

 

ES   

  95mm² 

   92-230-50-230-A 

Siba 2018920.400 400A   690V NH 00 

CL 

150mm² 

 116-230-50-230-A 

Siba 2071332.500 500A 1100V NH 1

 

CL 

150mm² 

 145-230-50-230-A 

Siba 2071332.630 630A 1110V NH 1

 

CL 

240mm² 

Table 3.6.1.6 

REVCON

®

 - type 

RLD D0 

Max. fuse  AC 

Connection terminal  

and max. Cross section  

of the supply line* 

 8-400-50-0-A 

Siba 5012406.20     20A   690V 10x38mm 

           ES 

  25mm² 

   11-400-50-0-A 

Siba 5012406.32     32A   690V 14x51mm 

ES 

  25mm² 

   18-400-50-0-A 

Siba 5012406.40     40A   690V 14x51mm 

ES 

  25mm² 

   28-400-50-0-A 

Siba 5014006.63     63A   690V 14x51mm 

ES 

  25mm² 

   38-400-50-0-A 

Siba 5014006.100 100A   690V 22x58 mm 

ES 

  25mm² 

   50-400-50-0-A 

Siba 2018920.160 160A   690V NH 00 

ES 

  25mm² 

   70-400-50-230-A 

Siba 2018920.160 160A   690V NH 00 

ES 

  50mm² 

 100-400-50-230-A 

Siba 2018920.160 200A   690V NH 00 

ES 

  95mm² 

 135-400-50-230-A 

Siba 2018920.350 350A   690V NH 00 

ES 

  95mm²  

 160-400-50-230-A 

Siba 2018920.400 400A   690V NH 00 

CL 

150mm²  

 200-400-50-230-A 

Siba 2071332.500 500A 1100V NH 1

 

CL 

150mm²  

 250-400-50-230-A 

Siba 2071332.630 630A 1110V NH 1 

CL 

240mm² 

 300-400-50-230-A 

Siba 2072332.800 800A 1100V NH 2 

CL  

240mm² 

Table 3.6.1.7

Summary of Contents for RLD B

Page 1: ...ELTROPLAN REVCON Elektrotechnische Anlagen GmbH Operating instructions Power feedback unit REVCON RLD E0 Power range 4 400 kW Voltage range 230V 400V 460V 500V 690V V 1 0 Issue 15 07...

Page 2: ...5 Residual hazards 16 2 6 General instructions 17 3 Technical data 29 3 1 Characteristics 29 3 2 General data application conditions 30 3 3 Rated data 31 3 3 1 Power feedback unit REVCON RLD B0 31 3 3...

Page 3: ...CON RLD D0 D1 88 4 4 1 3 Wiring schematic REVCON RLD B0 D0 with RHF RA 90 4 4 1 4 Wiring schematic REVCON RLD B0 D0 and FC with RHF RA 92 4 4 2 Fan supply 95 4 4 3 Control wires 95 4 4 4 Control funct...

Page 4: ...ystem All persons who work on and with the power feedback units REVCON RLD must have the Operation instructions available and observe all relevant notes and instruc tion The Operating Instructions mus...

Page 5: ...ed defects Claim Visible transport damages in transit immediately at the deliverer Visible deficiencies incompleteness immediately to ELTROPLAN REVCON RLD B0 033 400 50 0 A B Level B With internal mai...

Page 6: ...th direct DC Bus connection REVCON Type RLD D is required for drives with DC Bus connection via the DC choke s This unit contains additional capacity to compensate the magnetic energy from the DC chok...

Page 7: ...l drive systems Can be used on public and non public mains in industrial as well as residential and commercial premises The user is responsible for the compliance of this application with the EC direc...

Page 8: ...mity assessment procedure the conformity with the standards of the EC Directives is certified by fixing the CE marking Within the EC there are no trading obsta cles for a CE marked product Power feedb...

Page 9: ...DE 0160 11 94 Equipment of power installations with electronic components EN 61558 1 A1 Safety of power transformers power supplies reactors and similar products EN 60529 International protection rati...

Page 10: ...c standards Emission standard for residential commercial and light industrial environments DIN EN 61000 6 4 2007 A1 2011 IEC 61000 6 4 2006 A1 2010 Generic standards Emission standard for industrial e...

Page 11: ...improper handling Therefore it has to be avoided to get in contact with electronic components If electronic components are damaged mechanically the unit must not be put into operation as it cannot be...

Page 12: ...ied personal works at and with the power feedback unit The power feedback units are used in opposite to its purpose Power feedback units have to be projected in a way that they fulfil their function a...

Page 13: ...he corresponding standards and guidelines the operation on even for a short time over compensated networks cos 1 respectively on un choked com pensation units is not admissible If this is done neverth...

Page 14: ...ove lacquer Connect the cabinet or the plant by a star shaped network to ground ground loops have to be avoided The power feedback unit has been designed for a fixed connection to mains only Es pecial...

Page 15: ...an over current protection for an IT network an insulation supervision with pulscode measurment For all kind of networks protective insulation transformer may be used if required power and length of w...

Page 16: ...Qualified staff means persons that are entitled by the safety responsible due to their training experience education their knowledge in relevant norms directives accident directives and op eration con...

Page 17: ...ces by disregar Death or severe injuries arning of an mminent danger Warning Warns of a possible very situation Possible consequ Death or severe injuries angerous tuation Caution Warns of a possible d...

Page 18: ...device isn t a constant drain but it s dependent on the momentary characteristics of the supplying net Commutation brake downs and voltage flicker in the net have a considerable effect to the backward...

Page 19: ...ctors produce at a by the current carrying capacity defined cross section of the lead of the cable a maximum length of the connecting cable This inductivity always has to be higher or equal than the s...

Page 20: ...400V 33 40 RLD B 400V 45 100 RLD B 400V 70 220 RLD B 400V 90 220 RLD B 400V 135 440 RLD B 400V 160 660 RLD B 400V 200 660 RLD B 400V 225 660 RLD B 400V 250 880 RLD B 400V 345 1320 Table 2 6 1 REVCON t...

Page 21: ...sche Anlagen GmbH Example C 220 F UGL 100V 160A a 80mm r 8 5mm 0 1 257 10 6 H m lmax 26m For longer DC Bus wires additional capacitors have to be installed please get in contact with our application d...

Page 22: ...power of the motor connected to the inverter must be lower than half of the nomi nal power of the generator Second the total amount of the power of the two other loads must be more than double of the...

Page 23: ...io of the currents Generally the short circuit voltage of the transformer should be preferably small typical 4 6 Danger At non observance of these connecting conditions overvoltage and mains voltage h...

Page 24: ...t the load terminals of the commutation choke its inductivity prevents the synchronising to the supplying net and the induction voltage of the choke when it is switched of under load may result in dam...

Page 25: ...s of the conductors have to be low resistive and their number has to be reduced to the necessary minimum Too much or too high resistive terminals may result in an unsafe voltage magnification during t...

Page 26: ...ductors for frequency converters and power feed back operation Wire cross section mm Conductor radius mm Fuse A Max continuous current A 16 2 3 63 46 25 2 8 80 59 35 3 3 100 73 50 4 0 125 90 70 4 7 16...

Page 27: ...breaker the connec tion to the network energy sink and synchronising element for the power feedback unit misses The IGBT s now switch the DC voltage directly to the other loads The resulting nearly re...

Page 28: ...cause serious damages to the connected controller and or to the power feed back unit and to the other loads M 60kW FC Supplying network M FC M FC REVCON Figure 2 6 6 Note Same things apply to the str...

Page 29: ...usage of such an unchoked compensa tion plant are manifold direct resonance resonance rise switching transients or impairments of centralized ripple systems The fact that a company produces back effe...

Page 30: ...4kW to 400kW Up to 4 units can be paralleled more on request DC bus coupling of several controllers possible IGBT power modules with high efficiency and high service reliability Self synchronising Ove...

Page 31: ...DIN EN 60068 2 6 Test specification 5 Hz 13 2 Hz 150 Hz 2 mm peak to peak 0 7g Installation height h H 1000 m a m s l without power derating 1000 m a m s l h 4000 m a m s l with power derating Air pr...

Page 32: ...30 RLD B0 7 400 13 400 22 400 33 400 RLD B0 45 400 RLD B0 22 460 33 460 45 460 RLD B0 22 500 33 500 45 500 200 b RLD B0 38 230 50 230 75 230 RLD B0 70 400 90 400 135 400 RLD B0 70 460 90 460 110 460 1...

Page 33: ...0 RLD D0 28 230 RLD D0 8 400 11 400 18 400 28 400 38 400 RLD D0 50 400 RLD D0 15 460 24 460 33 460 RLD D0 17 500 27 500 37 500 45 500 RLD D0 24 690 45 690 200 b RLD D0 40 230 58 230 78 230 RLD D0 70 4...

Page 34: ...15 10 Mains frequency fN Hz 50 2 Overload capability ca 1 2 x Irms dynamic Efficiency Ca 97 Power factor 3 cos 1 Total harmonic distortion 3 THDI 16 Airflow requirement 1 m h a RLD B1 D1 7 400 13 400...

Page 35: ...current 65A refer to technical data nominal mesh voltage rating e g 400V From that results P 400V x 65A x 3 45033W that s about 45 0kW If the momentary RMS mains voltage is only 395V or even lower fo...

Page 36: ...010 RLD B0 225 400 50 230 A 325 389 21011111 RLD B0 250 400 50 230 A 360 433 21011112 RLD B0 345 400 50 230 A 498 602 21011113 Table 3 3 4 2 Nominal voltage 460V REVCON type AC Max current Irms A DC M...

Page 37: ...11027 RLD B0 140 500 50 230 A 161 195 21011028 RLD B0 160 500 50 230 A 185 224 21011029 RLD B0 250 500 50 230 A 289 347 21011030 RLD B0 400 500 50 230 A 462 559 21011131 Table 3 3 4 4 Nominal voltage...

Page 38: ...50 230 A 231 279 21014150 RLD D0 116 230 50 230 A 291 352 21014151 RLD D0 145 230 50 230 A 360 435 21014152 Table 3 3 5 1 Nominal voltage 400V REVCON type AC Max current Irms A DC Max current I A REV...

Page 39: ...minal voltage 500V REVCON type AC Max current Irms A DC Max current I A REVCON item number RLD D0 17 500 50 0 A 20 24 21014122 RLD D0 27 500 50 0 A 31 38 21014123 RLD D0 37 500 50 0 A 43 52 21014124 R...

Page 40: ...4 21015002 RLD D1 22 400 50 0 A 32 38 21015003 RLD D1 33 400 50 0 A 48 58 21015004 RLD D1 45 400 50 0 A 65 78 21015005 Table 3 3 6 2 3 4 Allowed operating data with maximal braking power Devices of pr...

Page 41: ...tion of braking time and intermission time is below the thermal limited power graph in the allowed area with forced cooling Remark Without forced cooling the intermission time is 8 minutes Example Nec...

Page 42: ...power 21 5 kW 27 kW 33 kW REVCON RLD B 33 XXX 1 Diagram 3 5 1 1 2 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 11 100 constant power with fan 26 kW 33 kW 45 kW min braking time min intermission time...

Page 43: ...ission time REVCON RLD B 90 XXX 1 90 kW Diagram 3 5 1 1 5 0 0 5 1 1 5 2 2 5 3 3 5 4 4 5 5 0 1 2 3 4 5 6 7 8 9 10 11 100 constant power 38 kW 52 kW min braking time min intermission time REVCON RLD B 1...

Page 44: ...ion time REVCON RLD B 200 XXX 1 200 kW Diagram 3 5 1 1 8 0 0 5 1 1 5 2 2 5 3 3 5 4 4 5 5 0 1 2 3 4 5 6 7 8 9 10 11 100 constant power 135 kW 170 kW min Braking time min Intermission time REVCON RLD B...

Page 45: ...ions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 0 0 5 1 1 5 2 2 5 3 3 5 4 4 5 5 0 1 2 3 4 5 6 7 8 9 10 11 100 constant power 200 kW 230 kW min Braking time min Intermission time REVCON RLD B...

Page 46: ...eedback unit as fol lowing tables refer to figure 4 4 1 1 to 4 4 1 4 position 1 The listed manufacturer is rec ommended but naturally also comparative fuses of other manufacturer e g Jean M ller Ferra...

Page 47: ...006 100 100A 690V 22x58mm ES 25mm 70 460 60 115 A Siba 2018920 160 160A 690V NH 00 ES 25mm 90 460 60 115 A Siba 2018920 200 200A 690V NH 00 ES 50mm 110 460 60 115 A Siba 2018920 250 250A 690V NH 00 ES...

Page 48: ...iba 5014006 100 100A 690V 22x58mm ES 25mm 28 230 50 0 A Siba 2018920 160 160A 690V NH 00 ES 25mm 40 230 50 230 A Siba 2018920 160 200A 690V NH 00 ES 50mm 58 230 50 230 A Siba 2018920 315 315A 690V NH...

Page 49: ...d max Cross section of the supply line 17 500 50 0 A Siba 5012406 32 32A 690V 14x51mm ES 25mm 27 500 50 0 A Siba 5012406 50 50A 690V 14x51mm ES 25mm 37 500 50 0 A Siba 5014006 80 80A 690V 22x58mm ES 2...

Page 50: ...nd Bussmann are suitable Stop If semiconductor fuses trip please get in contact with ELTROPLAN REVCON immediately as possibly further protective measures have tripped If internal fuses are exchanged p...

Page 51: ...LD B0 90 460 60 115 A Siba 2018920 200 200A 690V NH 00 RLD B0 110 460 60 115 A Siba 2018920 200 200A 690V NH 00 RLD B0 125 460 60 115 A Siba 2018920 250 250A 690V NH 00 RLD B0 140 460 60 115 A Siba 20...

Page 52: ...0 A Siba 5014006 80 80A 690V 22x58mm RLD D0 28 230 50 0 A Siba 5014006 100 100A 690V 22x58mm RLD D0 40 230 50 230 A Siba 2018920 160 160A 690V NH 00 RLD D0 58 230 50 230 A Siba 2018920 200 200A 690V...

Page 53: ...ing semiconductor fuses only RLD D0 17 500 50 0 A Siba 5012406 32 32A 690V 14x51mm RLD D0 27 500 50 0 A Siba 5014006 63 63A 690V 14x51mm RLD D0 37 500 50 0 A Siba 5014006 80 80A 690V 22x58mm RLD D0 45...

Page 54: ...ance of the category C2 Residential business and industrial environments a RFI filter can be connected to the power feedback unit according to figure 4 4 1 1 to 4 4 1 4 The power feedback units are as...

Page 55: ...12 31300102 50 45 460 60 115 A RFI RA 12 31300102 50 70 460 60 115 A RFI RA 23 31300103 50 90 460 60 115 A RFI RA 23 31300103 50 110 460 60 115 A RFI RA X5 31300106 70 125 460 60 115 A RFI RA X5 3130...

Page 56: ...0 A RFI RA 12 31300102 50 21 230 50 0 A RFI RA 12 31300102 50 28 230 50 0 A RFI RA 12 31300102 50 40 230 50 230 A RFI RA 23 31300103 50 58 230 50 230 A RFI RA X5 31300106 70 78 230 50 230 A RFI RA X5...

Page 57: ...Order designation filter Item Number Max Mains connection RFI cross section mm2 17 500 50 0 A RFI RA 12 31300102 50 27 500 50 0 A RFI RA 12 31300102 50 37 500 50 0 A RFI RA 12 31300102 50 45 500 50 0...

Page 58: ...REVCON RLD B1 D1 REVCON type RLD B1 D1 Order designation Order number Max Supply connection RFI cross section mm2 7 400 50 0 A RFI RA 12 31300102 50 13 400 50 0 A RFI RA 12 31300102 50 22 400 50 0 A...

Page 59: ...11 X5 inside RLD B0 90 400 50 230 A RHF RA 144 400 50 20 A 25070012 X6 inside RLD B0 135 400 50 230 A RHF RA 217 400 50 20 A 25070014 X7 inside RLD B0 160 400 50 230 A RHF RA 252 400 50 20 A 25070015...

Page 60: ...0 50 0 A 25070066 X5 inside RLD B0 90 690 50 230 A RHF RA 77 690 50 0 A 25070067 X6 inside RLD B0 150 690 50 230 A RHF RA 128 690 50 0 A 25070070 X6 inside RLD B0 200 690 50 230 A RHF RA 197 690 50 0...

Page 61: ...number Case type Fan RLD D0 17 500 50 0 A RHF RA 20 500 50 0 A 25070081 X4 inside RLD D0 27 500 50 0 A RHF RA 36 500 50 0 A 25070084 X4 inside RLD D0 37 500 50 0 A RHF RA 50 500 50 0 A 25070085 X5 ins...

Page 62: ...he power feedback unit may be impeded Take sufficient countermeasures e g separate cooling air mounting of air filters periodical cleaning Do not exceed the ambient temperature permissible during oper...

Page 63: ...1014 RLD B0 145 230 50 230 A 942 378 389 5 3 801 105 1300 RLD B0 200 230 50 230 A 942 378 389 5 3 801 123 1850 Table 4 2 1 1 Nominal voltage 400V REVCON Type Dimensions Enclosure Weight kg Power loss...

Page 64: ...8 389 5 3 800 110 1300 RLD B0 280 460 60 230 A 942 378 389 5 3 801 116 1580 RLD B0 325 460 60 230 A 942 378 389 5 3 801 118 1950 RLD B0 375 460 60 230 A 942 378 389 5 3 801 123 2430 Table 4 2 1 3 Nomi...

Page 65: ...0 50 230 A 942 378 389 5 3 801 100 1760 RLD B0 350 690 50 230 A 942 378 389 5 3 801 110 2150 Table 4 2 1 5 Nominal voltage 230V REVCON Type Dimensions Enclosure Weight kg Power loss W Height mm Width...

Page 66: ...389 5 3 800 99 1014 RLD D0 200 400 50 230 A 834 378 389 5 3 800 99 1300 RLD D0 250 400 50 230 A 942 378 389 5 3 801 105 1950 RLD D0 300 400 50 230 A 942 378 389 5 3 801 123 2430 Table 4 2 1 7 Nominal...

Page 67: ...al voltage 690V REVCON Type Dimensions Enclosure Weight kg Power loss W Height mm Width mm Depth mm RLD D0 24 690 230 0 700 274 315 2 700 35 160 RLD D0 45 690 230 0 700 274 315 2 700 65 350 RLD D0 70...

Page 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...

Page 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...

Page 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...

Page 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...

Page 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...

Page 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...

Page 74: ...e 1 and 2 are mounted in footprint housings which could be placed between cabinet wall and power feedback unit The radio interference filter of case type 3 and 4 are mounted in housings which should b...

Page 75: ...Installation 74 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Diagram RFI RA 12 3 Diagram RFI RA 23...

Page 76: ...Installation Operating instructions RLD 75 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Diagram RFI RA X5 5 Diagram RFI RA X6...

Page 77: ...Installation 76 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Diagram RFI RA X7 and X8 7 Diagram RFI RA V2 V4 und V7...

Page 78: ...Installation Operating instructions RLD 77 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 2 2 RHF RA filter 1 Diagram X1 2 Diagram X2...

Page 79: ...Installation 78 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Diagram X3 4 Diagram X4...

Page 80: ...Installation Operating instructions RLD 79 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Diagram X5 6 Diagram X5...

Page 81: ...Installation 80 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 7 Diagram X6 8 Diagram X7...

Page 82: ...Installation Operating instructions RLD 81 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 9 Diagram X8 Internal fan 10 Diagram X8 external fan...

Page 83: ...vities are started The exact values have to be cross checked with the documentation of the controller Replace defective fuses by the regular types chapter 3 3 3 2 only and without any live voltage 4 3...

Page 84: ...tage between L1 L3 and PE must not be higher than the nominal voltage With grounded active wire Allowed The voltage between L1 L3 and PE must not be higher than the nominal voltage Table 4 3 3 1 4 3 4...

Page 85: ...be considered refer to chapter 3 4 Protection of the wires at mains side L1 L2 and L3 by commercial wire protection fuses fuses have to be compliant with the relevant standards on site rated voltage...

Page 86: ...of the power unit The power feedback unit is equipped with a phase sequence control unit In case of an incorrect rotation field an error message is displayed via LED as follows rotation field failure...

Page 87: ...re 4 4 1 1 Wiring schematic of the power feedback unit REVCON RLD B0 B1 and one or more controller Note This is a wiring example Special features of an application e g installation of a PLC may re qui...

Page 88: ...f the wires is not reduced 4 Cross section in accordance with the relevant VDE rules 5 Fusing Supply 2A current input in accordance with DIN VDE 0298 or short circuit proof wiring 6 RFI filter optiona...

Page 89: ...re 4 4 1 2 Wiring schematic of the power feedback unit REVCON RLD B0 B1 and one or more controller Note This is a wiring example Special features of an application e g installation of a PLC may re qui...

Page 90: ...ses are used and if after 1 the cross section of the wires is not reduced 4 Cross section in accordance with the relevant VDE rules 5 Beginning with enclosure 2 Fusing 230V supply 2A current input in...

Page 91: ...Figure 4 4 1 3 Wiring schematic of the power feedback unit REVCON RLD B0 D0 with RHF RA and one or more controller Note This is a wiring example Special features of an application e g installation of...

Page 92: ...e 4 Cross section in accordance with the relevant VDE rules 5 Fusing Supply 2A current input in accordance with DIN VDE 0298 or short circuit proof wiring 6 RFI filter optional At RFI filter up to and...

Page 93: ...Figure 4 4 1 4 Wiring schematic of the power feedback unit REVCON RLD B0 B1 and FC with RHF RA and one or more controller Note This is a wiring example Special features of an application e g installa...

Page 94: ...ack unit To avoid such a situation the power feedback unit is equipped with an overvoltage switch off but nevertheless this hint should be observed 3 RHF RA module 4 Fusing in accordance with power fe...

Page 95: ...9 The ON or RESET signal may be initiated via terminals 11 and 12 Terminals 11 and 12 Positive pulse 12 24 V DC practicable e g via PLC terminal 11 terminal 12 10 Fan supply The power feedback module...

Page 96: ...e screening of the control wires with an as big as possible surface to the metal cable glands of the flange 4 4 4 Control functions The control terminal strip is placed on the control board and is ind...

Page 97: ...tion to driver board terminal X1 synchronisation to mains supply SW1 push button Quit Reset only version 1 4 1 terminal X2 ext messages and controlling terminal X4 connection to signalling board type...

Page 98: ...EVCON Elektrotechnische Anlagen GmbH Terminal usage Figure 4 4 4 2 Note The terminals 5 6 9 and 10 are not lead through 1 2 3 4 5 6 7 8 9 10 11 12 External OFF Not used ON RESET Terminal 5 and 6 inter...

Page 99: ...error is display as the relay toggles Terminals 5 and 6 These terminals are already used for the internal temperature supervision of the heat sink Terminals 7 and 8 Use screened wires only maximum le...

Page 100: ...s allows reducing the amount of power feedback units On the other hand several power feedback units may be coupled to transmit more power It s also possible to drive several motors at one inverter as...

Page 101: ...e of the mounting plates as possible e g with copper bands Ensure the separation of power and control cables Cable guides as close as possible to the reference potential Unguided cables have the same...

Page 102: ...ctive has to be carried out by the erector user of the machine plant If the by ELTROPLAN REVCON released RFI filters are used and the following measures and installation directives are observed the ad...

Page 103: ...grounding tapes Use copper or tinned copper screened wires only as steel screened wires are not suitable for high frequency applications Connect the screen with metal clamps or metal glands to the equ...

Page 104: ...gure shows mounting and connection of an external RFI filter Connected earth conductor Shield bus of copper connected superficially with the mounting plate Mounting plate Additional earthing strap Pow...

Page 105: ...etween RFI filter with power feedback unit DC and controller 9 Mounting plate common star point 3 RFI filter 10 Potential equalisation 4 Mains supply wire 11 Additional earthing wire 5 Wiring between...

Page 106: ...r The connection wire between power feedback unit and RFI filter must be screened At both ends the screen has to be connected to ground The wire should not be longer than 300mm The mounting plate of t...

Page 107: ...be connect ed to the screen bars to decrease the impedance of the screen The screen of digital signal wires which are connected to terminals has to be connected with as big surface as possible to gro...

Page 108: ...ack unit is possible 5 1 First powering up 1 Switch on mains supply The power feedback unit is ready for operation after ca 1s 2 Check the readiness for service of the power feedback unit If only the...

Page 109: ...Storage The unit is equipped with an error storage where special failures can be assigned to Stored error messages have to be confirmed by RESET or interruption of mains supply Storage always leads to...

Page 110: ...board Error storage ON means that the error phase failure is shown via LED until you confirm Error storage OFF how ever means that the error phase failure is shown via LED only as long as the failure...

Page 111: ...ctivate the phase failure supervision by removing the jumper J3 on the control board If after that a switch off with the indication via the red and yellow LED error code 3 happens an overvoltage will...

Page 112: ...collective error relay contact of the power feedback unit with the corresponding connection of the frequency inverter UCE tripping The power feedback unit trips by the UCE protective circuitry if the...

Page 113: ...REVCON Elektrotechnische Anlagen GmbH 7 1 LED messages LED display LED display Error code Operation Phase failure UCE Over temperature Disturbance Green Red Red Orange Yellow 1 X 2 X 3 X X X 4 X X 5...

Page 114: ...F Reset necessary Relay dropout 6 Overvoltage has been detected J8 closed After grid voltage has declined to its nominal value reset necessary Relay dropout 7 Rotary field orientation incorrect or one...

Page 115: ...ditions are observed refer to chapter 3 2 If the cooling air is polluted the cooling air input may be blocked Therefore check the power feedback unit periodically depending on the degree of pollution...

Page 116: ...nerator overload on the DC bus Such an overload normally may one of these three reasons 1 The power feedback unit is too small for the braking process In this case even with cur rent control no uninte...

Page 117: ...switching frequency of the power feedback unit increases from 150 Hz in standard operation up to 10 kHz In this operational mode the switching losses of the IGBT s increase rapidly This heat cannot b...

Page 118: ...erator panel in the door of the cabinet by using the external operating and signalling panel The external oper ating and signalling panel contains the complete display LED s of all running and failure...

Page 119: ...tional terminals A1 and A2 like below As long as no voltage is applied to A1 the power feedback unit will be completely off To turn it on apply 24V DC to A1 The unit will start up within the standard...

Page 120: ...sible Voltage controlled A free selectable output voltage in wide limits The required output voltage can be adjusted by set point 0 10V Current controlled A lower output voltage that adjusts free in d...

Page 121: ...08 The in these operating instructions contained details and technical data must be checked by the costumer before acquisition and application The costumer can raise no claims from these documents com...

Page 122: ...isolating lacquer 116 L low voltage directive 7 10 30 M Mains frequency 31 33 mains terminals 45 mains types 83 mounting position 61 O operating and signalling board external 117 operator s safety 16...

Reviews: