Resco GB3AAV Installation, Start-Up, And Operating Instructions Manual Download Page 15

The blower reverts to continuous operation after the heating cycle is completed.

When the thermostat "calls for cooling," the blower operates on cooling speed. When the thermostat is satisfied, the blower operates an
additional 90 sec before reverting back to continuous operation on heating speed.

4. Heat pump mode

When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off time during
demand defrost cycles. When the W-Y or W-Y-G thermostat inputs are received at the same time, the control changes the blower to heating
speed or starts the blower if it was off, and begins a heating cycle. The blower remains on until the end of the prepurge period, then shuts
off until the end of the ignition warm up and trial for ignition periods (a total of 24 sec). The blower then comes back on at heating speed.

When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to cooling speed after
a 1-sec delay. If the W-Y-G signals disappear at the same time, the blower remains on for the selected heating blower off delay period and
the inducer goes through its normal post-purge period. If the W-Y inputs should disappear, leaving the G signal input, the control goes into
continuous blower and the inducer remains on for the normal post-purge period.

Anytime the control senses false flame, the control locks out of the heating mode. This occurs because the control cannot sense the W input
due to the false flame signal and, as a result, sees only the Y input and goes into cooling mode blower off delay. All other control functions
remain in standard format.

NOTE:

EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized.

C.

Start-up Procedures

1. Purge gas lines—After all connections have been made, purge the lines and check for leaks.

WARNING: Never purge a line into a combustion chamber. Never use matches, candles, flame or other sources of

ignition to check for gas leakage. Use a soap-and-water solution to check for gas leaks. Failure to follow this warning could
result in fire, explosion, personal injury, or death.

2. Component test—The furnace control allows all components, except gas valve, to be run for a short period of time.

This feature helps diagnose a system problem in case of a component failure. To initiate component test procedure, short (jumper) the TEST
1/4-in. quick connect terminal on control board (adjacent to diagnostic light) and the C terminal on thermostat connection block for
approximately 2 sec. (See Fig. 11.)

NOTE:

Component test feature will not operate if any thermostat signal is present at control center.

Component test sequence is as follows.

a. Momentarily jumper TEST and C terminals until LED goes off.

b. LED will display previous fault 4 times.

c. Inducer motor operates for 10 sec, then stops.

d. Hot surface ignitor is energized for 15 sec, then de-energized.

e. Blower motor operates on cooling speed for 10 sec, then stops.

f. Blower motor operates on heating speed for 10 sec, then stops.

3. To operate furnace, follow procedures on operating instruction label attached to furnace.

4. With furnace operating, set thermostat below room temperature and observe that furnace goes off. Set thermostat above room temperature

and observe that furnace restarts.

D.

Adjustments

1. Set gas input rate.

There are 2 methods of adjusting the gas input rate. The preferred method is by using Table 7 and following instructions in item a. The
second method is by clocking the gas meter and following instructions in item b.

The gas valve regulator has been nominally set at 3.5-in. wc for natural gas. When adjusting input rate, do not set manifold pressure above
3.8-in. wc or below 3.2-in. wc.

a. Check gas input rate using Table 7.

(1.) Obtain average yearly heat value for local gas supply.

(2.) Obtain average yearly specific gravity for local gas supply.

(3.) Verify furnace model. Table 7 can only be used for model GB3AAV Furnaces.

(4.) Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.

CAUTION: DO NOT redrill burner orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive

burner noise and misdirection of burner flames. This can result in flame impingement of the burners and heat exchangers,
causing failure.

(5.) Find natural gas heat value and specific gravity in Table 7.

—15—

Summary of Contents for GB3AAV

Page 1: ...a Working Platform 7 Install Furnace 7 HORIZONTAL CRAWLSPACE INSTALLATION 7 8 FILTER ARRANGEMENT 8 9 GAS PIPING 9 10 ELECTRICAL CONNECTIONS 11 12 115 v Wiring 11 24 v Wiring 11 Accessories 11 12 VENTI...

Page 2: ...aces are available in sizes 50 000 through 135 000 Btuh input capacities The design of the downflow horizontal gas fired furnace is A G A C G A certified for natural and propane gas and for installati...

Page 3: ...monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury loss of life or property damage Consult a qualified installer service agency local gas supplier o...

Page 4: ...nds which include fluoride chloride bromide and iodide These elements are found in aerosol sprays detergents bleaches cleaning solvents salts air fresheners and other household products CAUTION The op...

Page 5: ...m outdoors See Fig 3 2 All air from outside the structure a If combustion air is taken from outdoors through vertical ducts the openings and ducts MUST have at least 1 sq in of free area per 4000 Btuh...

Page 6: ...8 19 7 16 21 19 7 8 19 5 8 19 7 16 24 1 2 23 7 16 19 5 8 19 7 16 These dimensions apply when a model CB or CD Evaporator Coil casing is to be installed B Installation On a Combustible Floor 1 Cut and...

Page 7: ...shield on platform in front of louvered control panel as shown in Fig 7 PROCEDURE 5 HORIZONTAL CRAWLSPACE INSTALLATION The furnace can be installed horizontally with either the LH or RH side up In a c...

Page 8: ...turn air plenum See Fig 8 and Table 4 for horizontal applications Horizontal filter retainers must be field supplied See Fig 9 for downflow applications Fig 6 Furnace Plenum and Subbase Installed on a...

Page 9: ...anadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction The gas supply line should be a separate line directly from the meter to the furnace if poss...

Page 10: ...d only to the male threads of the joints This pipe dope must be resistant to the action of propane gas Install an accessible manual shut off valve upstream of the furnace gas controls and within 72 in...

Page 11: ...n electrical shock fire or death B 24 v Wiring Make field 24 v connections at the 24 v terminal strip See Fig 11 Connect terminal Y as shown in Fig 13 for proper operation in cooling mode Use AWG No 1...

Page 12: ...08 230 VOLT SINGLE PHASE WHT BLK WHT BLK If any of the original wire as supplied must be replaced use same type or equivalent wire NOTE Connect Y terminal as shown for proper operation W Y GND THERMOS...

Page 13: ...Ignitor warm up At the end of the prepurge period the ignitor is energized for a 17 sec ignitor warm up period c Ignition sequence When the ignitor warm up period is completed the gas valve opens per...

Page 14: ...DISCONNECT SWITCH AND THE FURNACE JUNCTION BOX JB 5 THIS WIRE MUST BE CONNECTED TO FURNACE SHEETMETAL FOR CONTROL TO DETECT FLAME 6 FACTORY CONNECTED WHEN LGPS NOT USED 7 REPLACE ONLY WITH A 3 AMP FUS...

Page 15: ...e to follow this warning could result in fire explosion personal injury or death 2 Component test The furnace control allows all components except gas valve to be run for a short period of time This f...

Page 16: ...40 38 39 3 7 3 2 3 5 40 38 39 3 8 3 3 3 6 905 42 3 5 41 42 3 2 3 6 41 42 3 4 3 7 40 41 3 2 3 5 40 41 3 3 3 6 40 41 39 3 4 3 7 3 2 40 41 39 3 5 3 8 3 3 40 39 3 6 3 4 40 38 39 3 7 3 2 3 5 920 42 3 4 42...

Page 17: ...In the United States gas input on unit rating plate is for altitudes up to 2000 ft Ratings for altitudes over 2000 ft must be 4 percent less for each 1000 ft above sea level To obtain the adjusted al...

Page 18: ...0 60 62 64 66 68 60 58 56 54 53 120 116 112 109 106 300 290 281 273 265 25 26 27 28 29 144 138 133 129 124 288 277 267 257 248 720 692 667 643 621 70 72 74 76 78 51 50 48 47 46 103 100 97 95 92 257 25...

Page 19: ...g the heating cycle length NOTE When using an electronic thermostat set cycle rate for 3 cycles per hr E Check Safety Controls The flame sensor gas valve and pressure switch were all checked in the St...

Page 20: ...did not function properly and correct condition e Turn off 115 v power to furnace f Reconnect inducer motor wires replace control door and turn on 115 v power to furnace 4 Check auxiliary limits when...

Reviews: